Haier AP88NACBEA Operation Manual - Installation Procedure
Matters needing attention
Never use oxygen,flamable and poisonous gases for the leak test.
Step 1:Charge for more than 3 minutes under 0.3MPa(3.0kg/cm
2
g)
Step 2:Charge for more than 3 minutes under 1.5MPa(15kg/cm
2
g)
--Serious leakage may be found.
Step 3:Charge for more than 24 hours under 3.0MPa(3.0kg/cm
2
g)
--Small leakage may be found.
Check for pressure decrease
Without pressure decrease-Pass
With pressure decrease-Check for leaage.
There will be a 0.01MPa(0.1kg/cm
2
g) pressure change for every 1 C ambient temperature change during
the 24-hour pressure charge.It should be corrected during the test.