Haier AU282XHERA Installation Manual

Other manuals for AU282XHERA: Service Manual, Installation Manual
Manual is about: X MULTI SERIES

Summary of AU282XHERA

  • Page 1

    R410a multi split series room air conditioner outdoor unit installation manual au282xhera au342xhera please read this manual carefully before installing the units. Please keep this manual safely for future use. No.0010577255 a.

  • Page 2: Contents

    Cautions ....................................................................................................................... Safety precautions........................................................................................................ Installation accessories...........................

  • Page 3: Cautions

    Cautions 1 disposal of the old air conditioner before disposing an old air conditioner that goes out of use, please make sure it's inoperative and safe. Unplug the air conditioner in order to avoid the risk of child entrapment. It must be noticed that air conditioner system contains refrigerants, wh...

  • Page 4: Cautions

    4. The wiring method should be in line with the local wiring standard. 5. The power cable and connecting cable are self- provided. All the cables shall have got the local authentication certificate. During installation, when the connecting cables break off, it must be assured that the grounding wire...

  • Page 5: Safety Precautions

    3 safety precautions all units shall be earthed. The earth must not be connected to a gas pipe, water pipe, or telephone line. Poor earthing could cause electric shock. Be sure to install a circuit breaker to avoid electric shock. Arrange water drainage according to this manual. Cover pipe with insu...

  • Page 6: Safety Precautions

    4 (c) where there is strong radiation. It will affect the unit's control system, causing malfunction of the unit. (d) where there are flammable gas, dirt, and volatile matter (thinner, gasoline) exist, these items will cause a fire risk. The following accessories are supplied together with the outdo...

  • Page 7

    5 1. Do not connected the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in ordor to add another indoor unit later. Make sure no dirt or mositure gets into eigher side of the embedded branch piping. 2.It is impossible to connect the ...

  • Page 8

    6 matching of the indoor and outdoor units remark 07 09 12 12 14 14 18 07 07 07 07 07 07 07 09 09 09 09 09 09 12 12 12 12 12 14 07 07 07 07 07 07 07 07 07 07 07 07 07 09 09 09 09 09 09 a b 18 18 14 18 14 18 18 07 07 07 09 09 09 09 09 09 09 09 12 12 12 12 12 14 14 14 07 07 07 07 07 07 07 07 07 09 09 ...

  • Page 9

    7 matching of the indoor and outdoor units remark 12 14 14 18 07 07 07 07 07 09 09 09 09 09 09 12 12 12 12 12 14 14 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 09 09 09 09 09 09 09 12 a b 18 14 18 18 07 07 09 09 09 09 09 09 09 12 12 12 12 12 14 14 14 14 07 07 07 07 07 07 07 07 07 07 07 09 09 ...

  • Page 10: Power Source

    8 outdoor unit capacity class piping to each indoor unit total length of liquid piping between all units au282xhera au342xhera 25m max. 60m max. 2.Selecting a location for installation of the indoor units 1.Precautions on installation before inserting power plug into receptacle, check the voltage wi...

  • Page 11

    9 the piping length information, please refer the following table. Descriptions standard a, b, c,d liquid pipe a, b, c,d gas pipe mm item maximum unit l1 (one way) l2 (one way) l3 (one way) h h + h - mm m m m m m m size of the liquid side connection pipe pipe length when the compressor connects with...

  • Page 12: Refrigerant Piping Work

    10 refrigerant piping work forced fastening without careful centering may damage the threads and cause a leakage of gas. Pipe diameter ( ) fastening torque liquid side 6.35mm (1/4'') 18n.M gas side 9.52mm (3/8'') 50n.M 3. Attaching drain-elbow if the drain-elbow is used, please attach it as figure. ...

  • Page 13: Refrigerant Piping Work

    11 4.Cutting and flaring work of piping pipe cutting is carried out with a pipe cutter and burs must be removed. After inserting the flare nut, flaring work is carried out. Less than 5cm it becomes high midway. The end is immersed in water it waves. It gap with the ground ts too small. There is the ...

  • Page 14

    12 in case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed 6 steps. 9.52mm (3/8") 6.35mm (1/4") 9.52mm (3/8") 6.35mm (1/4") 9.52mm (3/8") 9.52mm (3/8") 6.35mm (1/4") 6.35mm (1/4") to indoor unit c to indoor unit d to indoor unit b 2 way valve 3 way valve to indoor un...

  • Page 15: Wiring Work

    1. Electric wiring note: the air conditioner must use special circuit , and wiring by the qualified electrician according to the wiring rules specified in national standard. The grounding wire and the neutral wire shall be strictly separated. Connect the neutral wire with grounding wire is incorrect...

  • Page 16: Wiring Work

    14 3. Wiring method of outdoor unit: loosen wire cover and connect the power line and communication wire of indoor unit to the terminal correspondingly. Note: when connecting power line to power supply terminal, please pay attention to the following items: do not connect the power line with differen...

  • Page 17: Wiring Work

    15 5. Example wiring diagram. Please refer to the indoor unit installation manual to find detailly how to set and check the communication address. Incorrect address setting will cause abnormal to the system. 6. After installation, please fill in the following table for easy daily maintenance: indoor...

  • Page 18: Items to Confirm

    16 items to confirm test running before starting the test running, please confirm the following works have been done successfully. 1) correct piping work; 2) correct wiring work; 3) correct match of indoor and outdoor unit; 4) proper recharge of refrigerant if needed; 5) correct indoor unit addresse...

  • Page 19: Trouble Shooting

    17 trouble shooting failure code state of led 5-4-3-2-1 trouble shooting possible reasons dc fan motor fault fan is blocked, or the terminal is disconnected from the pcb faulty 4-way valve switching on coil of 4-way valve is disconnected, or faulty outdoor pcb abnormal communication between main pcb...

  • Page 20

    Haier group qingdao haier air conditioner electric co., ltd. Address: haier garden, qianwangang road, economic development zone, qingdao, shandong 266555, p.R.China web site: http://www.Haier.Com.