IBC VFC 15-150 Operating Instructions Manual

Summary of VFC 15-150

  • Page 1

    1 vfc 15-150 / vfc 45-225 natural gas conversion parts kit# p-176 120-170 r2 danger check the rating plate of the boiler to ensure it is configured for the fuel you are using. Failure to perform the proper fuel conversion when required can result in an immediate hazard. Operating any ibc boiler usin...

  • Page 2

    2 vfc 15-150 / vfc 45-225 natural gas conversion parts kit# p-176 120-170 r2 refer to the details in the boiler’s current installation and operation manual, section 3.3 - “commissioning”, 3.4 “fuel conversion” the low fire (zero-offset) valve and high fire (gas: air) ratio adjustment will have to be...

  • Page 3

    3 vfc 15-150 / vfc 45-225 natural gas conversion parts kit# p-176 120-170 r2 1. Turn off the boiler’s gas shut off valve. With a small (1/8” or 3 mm) flat screwdriver, open the inlet gas supply pressure test port by turning its center- screw 1 full turn counterclockwise. Attach a manometer to the pr...

  • Page 4

    4 vfc 15-150 / vfc 45-225 natural gas conversion parts kit# p-176 120-170 r2 note the installer must fill in the information and affix the included fuel conversion labels to the boiler in the positions indicated after the conversion is completed.