Jackson Systems Comfort System T-32-P Installation Manual

Other manuals for Comfort System T-32-P: Installation Manual, Operation Manual
Manual is about: Universal Thermostat

Summary of Comfort System T-32-P

  • Page 1

    Installation manual comfort system t-32-p universal thermostat tm version 1.4.

  • Page 2

    This manual should not be left with the owner as it contains installer setup functions which, if not correctly set, may cause damage to the hvac equipment or seriously affect performance. Although great care has been taken in the preparation of this manual, jackson systems takes no responsibility fo...

  • Page 3

    As with any hvac project, careful installation is the key to a successful outcome. Time taken during the installation process will be rewarded by fewer call-backs. The steps required to install the t-32-p thermostat are as follows: 1. Read and understand this installation manual and user manual. 2. ...

  • Page 4

    4 installing the thermostat w2 g3 y2 g2 w1 o/by1 g1 r 24 24c b a t t factory jumper power coms aux figure 3 terminal designations based on the t-32-p slide switch configurations, some terminals have multiple output functions. (figure 3) terminal designation chart terminal designation w2 y2 w1 o/b y1...

  • Page 5

    Typical system wiring diagrams w2 g3 y2 g2 w1 o/b y1 g1 r 24 24c b a t t rev valve fan 1 relay modbus tt terminals line comp 1 relay aux heat 24 v 2 heat / 1 cool heat pump switch settings sw1 = off (fan relay) sw2 = on (heat pump) sw3 = off (single stage) sw4 = reversing valve (off = ‘o’ - rv energ...

  • Page 6

    6 special instructions for dual fuel applications when the t-32-p is used with dual fuel systems, an outdoor sensor is recommended for balance point control (model t-32-s1). The sensor is wired to the tt terminals on the thermostat. In the , set this configures the thermostat to receive the outdoor ...

  • Page 7

    7 entering the advanced installer settings menu entering the advanced installer settings menu the t-32-p contains factory defaults for all advanced installer settings. Depending upon the user and equipment application, some settings may need to be changed. To enter the advanced installer settings me...

  • Page 8

    Advanced installer settings menu symbol default function sp 2 1.9° f differential for stage 1. Sp=1 - 1.4° f differential. Sp=3 - 2.4° f differential. Sd 2 1.9° f differential for stage 2. Sp=1 - 1.4° f differential. Sp=3 - 2.4° f differential. Dt 20 upstage timer. (adjustable from 10 - 90 minutes i...

  • Page 9

    Tt terminal functions indoor sensor wiring when the t-32-s1 is used as an indoor sensor, the t-32-p can be configured to allow only the remote sensor to control the temperature (tt=rs) or both the remote and onboard sensor can be used for temperature averaging (tt=av). An optional in-line switch can...

  • Page 10

    Factory test mode equipment should be disabled when performing this test. Fan the t-32-p contains a simple factory test mode that can confirm relay outputs, slide switch configuration along with a factory default reset. Ts=0 - factory test mode is off ts=1 - displays system configuration code based ...

  • Page 11

    Specifications input voltage 24 vac 50/60 hz relay rating 24 vac @ 1amp maximum per relay operating temperature 32° f to 122° f operating rh 0-95% (non-condensing) storage temperature 32° f to 105° f size 4-7/16” w x 4-1/16” h x 7/8” d lcd display size 2-3/4” w x 1-7/8” h temperature sensor 10k ntc ...