Lap RH60B-LED Installer's Manual - page 4
UNDERSTANDING THE CONTROLS ---- Referring to Fig. (3)
ADJUSTING THE DURATION TIME: The length of time that the light remains switched on after
activation can be adjusted from (10±5) seconds to (4±1) minutes. Rotating the TIME knob from (+)
to (-) will reduce the duration time.
Note: Once the light has been triggered by the PIR sensor any subsequent detection will start the
timed period again from the beginning.
ADJUSTING THE LUX CONTROL LEVEL: The Lux control module has a built-in sensing device
(photocell) that detects daylight and darkness. The ( ) position denotes that the bulkhead light
can work at day and night, and the ( ) position only work at night. You can set to operate the unit
at the desired level by adjusting the LUX knob.
1. Installation should be carried out by a licensed electrician and according to IEC wiring
Regulations.
2. Switch power off at the meter box and ensure that there is no power to the lamp.
3. Remove the
Lampshade using a screwdriver, see fig 2
4. Unscrew the
Screw (A) and remove the Transparent Plate.
5. Mark the mounting hole positions onto the wall. Drill and plug the wall at the marked positions.
Screw the lamp body to wall with suitable
Mounting Screws (supplied)
6. Connect the main power wires (H05RN-F 3G 1.0mm2 ) to the
Terminal Block (noting the correct
terminals in fig .2), the
Cable must pass through the Wiring Rubber Gasket.
7. Re fit the
Transparent Plate.
8. Re-fit the
Lampshade by hand.
9. Once the bulkhead light has been installed, the detection area and PIR Sensor can be adjusted.
■
NOTES FOR ELECTRICIAN-- Installation by a licensed electrician
1) The Bulkhead Light should be wired to its own lamp switch. Do not interconnect with
other lights on the same switch.
2) Do not connect to Dimmer.
Fig. (3)