2.3.3 Status Messages
Display Message
BriefDescription
Solution
No Probe
No probe connected to
transmitter
Checkprobeconnectiontotransmitter,ConsultFactory
New Probe
Probememorycontents
disagree with EEPROM image
OnDisplay,goto‘ResetNewProbe’andenterpassword.
Analog Board Error
No response from co-
processor, or clock error
ConsultFactory.
ProbeMemoryError Memorydeviceinprobeis
unresponsive
ConsultFactory.
No Float Detected
Echo curve does not rise above
threshold
Run echo curve. If a visible peak exists, increase gain/
sensitivity.Ifthereisnopeak,visuallyinspectprobeto
confirmpresenceoffloat.Iffloatstillnotdetected,consult
factory.
ConfigConflict
MeasurementTypeand
PrimaryVariableselection
parameters are inconsistent
ConfirmmeasurementtypematchesPV.GoodExamples:
1. MT=LevelOnly,PV=TotalLevel
2. MT=Level&IFC,PV=IFC
High Volume Alarm
Level exceeds highest level in
strapping table or top of vessel
bymorethan5%
Confirmspansetpointsareatdesiredvalues.
Run echo curve. Check for noise at top of probe. If top
mount or direct insertion unit, increase deadband/blocking
distance
Extra Float Detected Echo curve rises above
threshold additional instance
from expected number
CheckMeasurementtype;Runechocurvetocheckfor
extrapeaks;DecreaseGain/SensitivitySettings;Swipe
probewithpocketmagnettoeliminatepossibilityof
residualmagnetism;ConsultFactory.
2nd Float Missing
Echo curve rises above
thresholdonlyonce
CheckMeasurementtype;Runechocurve;IncreaseGain/
SensitivitySettings;Verifytwofloatsarepresent.Consult
Factory.
High Elec Temp
Present electronics temperature
above maximum
Take measures to cool transmitter head. Consider
installing sunshade.
Low Elec Temp
Present electronics temperature
below minimum
Take measure to warm transmitter head. Consider
installing heat tracing.
AdjustAnalogOut
Loop trim parameters are at
default values
Perform Trim Loop Current Check via HART
Communication
LowSupplyVoltage Powersupplyvoltage
inadequate to prevent brownout
or reset
Checksupplyvoltage.
Weak Upr Echo
Strengthofechofromfloatat
gas-liquid interface less than
allowable minimum
Runechocurve.IncreaseGain/SensitivitySettings.
ConsultFactory.
Weak Ifc Echo
Strengthofechofromfloatat
liquid-liquid interface less than
allowable minimum
Runechocurve.IncreaseGain/SensitivitySettings;
Consult
Factory.
High Noise/Lvl
Threshold
Strength of baseline noise too
near upper level threshold
Check echo curve for noise levels.
EchoRejectionmayberequired,Consult
Factory,Swipeprobewithpocketmagnettoeliminate
possibilityofresidualmagnetism
High Noise/Ifc
Threshold
Strength of baseline noise too
near interface level threshold
Check echo curve for noise levels.
EchoRejectionmayberequired,Consult
Factory,Swipeprobewithpocketmagnettoeliminate
possibilityofresidualmagnetism
2.3.4 Diagnostic Help
Selecting DIAGNOSTICS from the MAIN MENU presents a
list of five ITEMS from the top level of the DIAGNOSTICS
tree.
When Present Status is highlighted, the highest MAGNETROL
priority active diagnostic indicator (numerically lowest in Table
3.3.3) is displayed on the bottom LCD line, which is “OK”
as shown at left. Pressing the ENTER key moves the active
diagnostic indicator to the top line outdented and presents in
the lower area of the LCD a brief explanation of and possible
remedies for the indicated condition. A blank line separates the
explanation from the remedies. Additional active diagnostic
indicators, if any, appear with their explanations in descending
priority order. Each additional active indicator name-explanation
pair is separated by a blank line from the one above.
If the explanation and remedy text (and additional name expla-
nation pairs) exceeds the available space, a appears in the right-
most column of the last line indicating more text below. In this
situation, the DN key scrolls text up one line at a time. Similarly,
while text exists above the upper line of the text field, a appears
in the rightmost column of the top (text) line. In this situation,
the UP key scrolls the text down one line at a time. Otherwise
the DN and UP keys are inoperative. In all cases the ENT or
DEL key reverts to the previous screen.
When the transmitter is operating normally and the highlight
cursor is positioned on Present Status, the bottom LCD line
displays “OK” because no diagnostic indicators are active.
EVENT HISTORY
– This menu displays the parameters related
to diagnostic event logging.
ADVANCED DIAGNOSTICS
– This menu displays parame-
ters related to some of the advanced diagnostics available within
the Model JM4.
INTERNAL VALUES
– Displays read-only internal param-
eters.
ELEC TEMPERATURES
– Displays temperature informa-
tion as measured in the potted module in degrees F or C.
TRANSMITTER TESTS
– Allows the user to manually
set the output current to a constant value. This is a method
for the user to verify operation of the other equipment in
the loop.
ECHO CURVES
– This menu allows the user to display the live
Echo Curve and Echo Rejection on the LCD.
DIAGNOSTICS
Present Status
EVENT HISTORY
ADVANCED DIAGNOSTICS
ECHO CURVES
ECHO HISTORY
OK
DEVICE FAILURE
No Probe
Fig. 2-3. Diagnostics Menu
Fig. 2-4. Status Message - No Probe