Nailor BAC-8001-36 Installation And Operation Manual - page 16
IOM-EZVAVINST
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Page 16 of 48
Installation and Operation Manual
●
EZvav Digital Controls
Proceduretosetthetemperaturesetpoints(continue)
PROCEDURE
STEPS
STEDISPLAY
5 Set the occupied cooling set point.
This set point is used as the active set point when the
space is occupied.
1. Press the
∆
or
buttons to set the occupied
cooling set point. The set point will change in 0.5°
increments.
2. Press the button to save the set point and
advance to the next function.
Note: This set point can also be changed as described in
the topic Changing the room set point on page 13.
6 Set the occupied heating set
point.
This set point is used as the active set point when the
space is occupied.
1. Press the
∆
or
buttons to set the occupied
heating set point. The set point will change in 0.5°
increments.
2. Press the button to save the set point and
advance to the next function.
Note: This set point can also be changed as described in
the section Changing the room set point on page 13.
7 Set the unoccupied cooling set
point.
This set point is used as the active set point when the
space is unoccupied.
1. Press the
∆
or
buttons to set the unoccupied
cooling set point. The set point will change in 0.5°
increments.
2. Press the button to save the set point and
advance to the next function.
8 Set the unoccupied heating set
point.
This set point is used as the active set point when the
space is unoccupied.
1. Press the
∆
or
buttons to set the unoccupied
heating set point. The set point will change in 0.5°
increments.
2. Press the button to save the set point and
advance to the next function.
9 Set the supply air temperature
changeover set point.
Not used in all models.
This set point sets the supply air temperature at which
the controller will change between heating to cooling.
1. Press the
∆
or
buttons to set the changeover set
point. The set point will change in 1° increments.
2. Press the button to save the set point and
advance to the next function.
10 Set the minimum temperature
differential set point.
The minimum allowable temperature value between
the cooling and heating set points.
1. Press the
∆
or
buttons to set the differential set
point. The set point will change in 1° increments.
2. Press the button to save the set point and
advance to the next function.
∆
∆
∆
∆
∆
∆