Nailor BAC-8001-36 Installation And Operation Manual - page 26
IOM-EZVAVINST
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Page 26 of 48
Installation and Operation Manual
●
EZvav Digital Controls
Theairflowbalancingprocedure(continue)
PROCEDURE
STEPS
STEDISPLAY
4 Measure and enter the actual
minimum primary airflow.
The display begins flashing PMIN and also displays
the actual airflow at the bottom.
Note: The airflow will attempt to stabilize on the
lowest value for either the cooling or heating minimum
airflow even if only one mode is operational.
Note: The airflow displayed by the STE-8000 in this
step is the actual, uncorrected airflow.
1. Wait for the minimum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the button to advance to the entry display.
PMIN
stops flashing.
4. Press the
∆
or buttons to enter the measured
airflow.
5. Press the button to save the measured airflow.
The display advances to PRI.
5 Advance or exit.
1. Press the
∆
or buttons to select one of the
following:
• SEC to balance the secondary VAV for dual duct
systems. Choosing SEC advances to the SMAX
display. This is available only on dual duct models.
• BACK to choose another commissioning function
• EXIT to return to the temperature display.
2. Press the button to select the next function.
6 Measure and enter the actual
maximum secondary airflow.
The display begins flashing SMAX and also displays
the actual airflow at the bottom.
Note: The airflow displayed by the STE-8000 in this
step is the actual, uncorrected airflow.
1. Wait for the maximum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the button to advance to the entry display.
SMAX
stops flashing.
4. Press the
∆
or buttons to enter the measured
airflow.
5. Press the button to save the measured airflow.
The display advances to SMIN.
7 Measure and enter the actual
minimum secondary airflow.
The display begins flashing SMIN and also displays
the actual airflow at the bottom.
Note: The airflow displayed by the STE-8000 in this
step is the actual, uncorrected airflow.
1. Wait for the minimum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the button to advance to the entry display.
SMIN
stops flashing.
4. Press the
∆
or buttons to enter the measured
airflow.
5. Press the button to save the measured airflow.
The display advances to SEC.
∆
∆
∆
∆