    Xp-600 & rpxp6gt keypad control panel/communicator installation instructions wi1372 1/05 © napco 2005 ®.

  • Page 2

    2 wi1372 xp-600 installation instructions general information the napco express xp-600 control panel provides up to 6 hardwired/wireless zones and 2-wire fire. Up to six 4-digit user codes can be programmed. Ambush, when selected, uses user 6 code as an ambush code. The xp-600 is wireless ready. Whe...

  • Page 3

    3 specifications current & voltage ratings residential burglary (4 hour standby) combined standby current: -------------- 500 ma bell output: ----------------------------------- 2 a (using rechargeable 12 vdc 4 ah battery, minimal requirement) residential fire (24 hour standby) combined standby curr...

  • Page 4

    4 wi1372 xp-600 installation instructions mfg 4-wire smoke detector smoke detector base sentrol 449at 449c 449crt 449cst 449csrt 449csst 449clt 449cslt 449cte 741u 712u 722u 732u 711u 721u 721ut 731u 701u 702u 702re 702ru system sensor 1112 2112 2112t 2112tsrb 2100 2100t 1100 2-wire smoke detector 6...

  • Page 5

    5 programming the panel refer to xp-600 programming instructions (wi1373) defaulting the panel 1. Remove power from the panel. 2. Remove all wiring from terminal 15 (pgm) and terminal 3. 3. Connect terminal 15 (pgm) to terminal 3. 4. Apply power to the xp-600 control panel. 5. After a few seconds th...

  • Page 6

    6 wi1372 xp-600 installation instructions installation mounting the panel mount the panel close to an unswitched ac source, a cold-water pipe ground, and a telephone line connection. Mounting the keypad a keypad should be located near an exit/entry door. To remove the keypad from the backplate, inse...

  • Page 7

    7 burglary zone wiring napco’s ez zone doubling tm is simple. Each terminal has 2 zones, use an e (2.2 k) type zone doubling resistor for the primary zone and a z (3.9 k) type zone doubling resistor for the secondary zone. Wire zones as shown in the wiring diagram at the back of this manual (page 27...

  • Page 8

    8 wi1372 xp-600 installation instructions keypad leds w armed led definition armed on instant mode rapid flash zone in alarm flashing x ready led definition ready to be armed on zone faulted off hsystem led definition ac failure flashing system trouble(s) on fire led definition fire alarm flashing f...

  • Page 9

    9 delay tone. Enter a valid arm/disarm code. If a valid arm/disarm code is entered, the keypad will beep 6 times, indicating the panel has been disarmed. The red armed led will go out. If an incorrect arm/disarm code is entered, the keypad will sound a 1-second tone, indicating incorrect entry. Pres...

  • Page 10

    10 wi1372 xp-600 installation instructions to change the user 1 code from its default value of 1234, program the 4-digit user 1 code through dealer programming [95]. User 1 arm/ disarm code is also used to program user codes 2 - 6. By default, the user 1 code cannot be re-programmed by the user. If ...

  • Page 11

    11 a 8 + user 1 code - user program mode a 9 keypad sleep mode on/off enter this command to turn the keypad sounder on/off. When the keypad is in sleep mode all keypad sounds will be silenced except for keypad feedback beeps and keypad sounder on alarm. User commands - optional a 0 easy exit/easy ar...

  • Page 12

    12 wi1372 xp-600 installation instructions remote activation using napco’s quickloader software (version 3.26 or higher), follow the instructions below: from the status screen press f6 select miscellaneous control select enable signal strength logging uploading signal strength information from the l...

  • Page 13

    13 an alarm condition. [04]24-hour protection a zone that provides protection at all times, whether or not the system is armed. [05]40 ms loop response normally loop response is 750 ms, select this option to change the loop response to 40 ms. The slower the loop response, the less sensitive the syst...

  • Page 14

    14 wi1372 xp-600 installation instructions [15]line cut time-to-fail enable this feature by programming the delay time required to declare a line cut failure. Programming 000 will disable line cut detection. [16]wireless supervisory timer a transmitter will send a transmission every time it is tripp...

  • Page 15

    15 [22]miscellaneous features 1 (1) abort delay - program to allow a 15 second delay (except 24 hour zones) after a zone trip before reporting. Disarm the system within 15 seconds to prevent reporting. (2) easy exit/easy arm - enables a 0 command. While the system is armed, entering this command all...

  • Page 16

    16 wi1372 xp-600 installation instructions then press the i key to blank the last digit. [31]telephone number 1 program the phone number to be dialed for telephone number 1. Program the number directly, just as it is entered on a touchtone phone. A fixeddial tone detection (e) is included prior to t...

  • Page 17

    17 battery restore report. (3) trouble restore - program to activate a trouble restore report. (4) fire restore - program to activate a fire restore report. [39]opening/closing report, telco 1 select users required to send opening and closing reports to telephone number 1. Do not program for users t...

  • Page 18

    18 wi1372 xp-600 installation instructions [47]leading digits pager pin number - if a pin number is required by the paging system, program the pin number in the leading digits location. See sample program below. If a 7-digit pin number is required, program the panel as follows: [31]/[41]/[51] - page...

  • Page 19

    19 system report code [63]. For example, if a low battery system report code is f8 the battery restore would be e8 (4/2 format). [65]opening and closing codes program opening and closing codes for users 1 through 6. The second digit of the report code is the number of the user that armed or disarmed...

  • Page 20

    20 wi1372 xp-600 installation instructions strength logging mode - pg. 11). [71-76] wireless transmitters enter the rf id# and the point number that is to be mapped to the zone. Programming example map point 1 of a window door transmitter with an rf id# of 0012b0:0 to zone 3. 1. Enter dealer mode. 2...

  • Page 21

    21 8 interior program an 8 in the aux 1 and/or aux 2 option to bypass exit/entry follower zones or home/away with delay zones when the m or n buttons on the keyfob are pressed (only if the system is programmed exclusively for home/away with delay zones). [85] - [88] wireless smoke detectors enter th...

  • Page 22

    22 wi1372 xp-600 installation instructions the computer is now in standby site at the site perform the following three steps: • arm the panel. • disarm the panel. • enter a 6 . The panel will now call the download computer running pcpreset. Pcpreset will answer the call, establish a connection, and ...

  • Page 23

    23 system troubles use the system trouble chart on the following page to determine the specific system trouble(s). During normal panel operation the h system trouble led has the following two modes of operation: steady 1-7 possible trouble groups, ac is present flashing 1-7 possible trouble groups, ...

  • Page 24

    24 wi1372 xp-600 installation instructions keypad beeps or h system flashes zone led on system trouble condition cause/action 1 beep 1 ac power failure this trouble will occur if ac power is not present. Ensure that the transformer is connected to an unswitched power source. 2 low battery if there h...

  • Page 25

    25 troubleshooting 1. The bell output drops to about 3 volts in alarm. The battery/bell circuit is protected by a pc board trace which may have burned open by reversal of the battery leads. It is on the back of the pc board just adjacent to the red & black battery leads. Send in for service if this ...

  • Page 26

    26 wi1372 xp-600 installation instructions 8. How do i remove keypad sounder on alarm? The keypad sounder follows the burg output. If you need to remove the keypad sounder, then you must remove the burg output from that zone. 9. Transmitters not responding? Open transmitter case - keypad should go i...

  • Page 27

    27 -4 +5 +6 xp-600 terminals 1 2 +3 gem-recv-xp8 16 vac 20 va transformer napco trf12 (or equivalent see wi1372). Class 2 transformer. Do not connect to switched outlet. + red (+) + black e1 e2 rechargeable battery 12 vdc 4ah or 7ah this equipment should be installed in accordance with chapter 2 of ...

  • Page 28

    28 wi1372 xp-600 installation instructions napco limited warranty napco security systems, inc. (napco) warrants its products to be free from manufacturing defects in materials and workmanship for thirty-six months following the date of manufacture. Napco will, within said period, at its option, repa...