When a failure occurs the controller exits the RUN mode and goes to the FAILURE mode and displays
the failure message. The alarm will sound and remain on until it is silenced by the user. The Info key can
be pressed to silence the alarm. Once the alarm is silenced it can be reset by pressing the Info key and
then the Stop key. This returns the controller to the OFF mode.
The failure is recorded in the event log accessible from the Basic Menu.
4.10 WARNINGS AND FAILURES (CONT’D)
When the generator is started and load is detected on the generator when the WaveNet is in the RUN
mode the “Genset Online” LED on the WaveNet front panel will turn green. This indicates that the gen-
erator is supply load as normal. If load is detected on the generator when it is not in the RUN mode (e.g.
the WaveNet is cranking, preheating, etc.) the WaveNet terminates starting and enters the FAILURE
mode and the “Genset Online” LED on the WaveNet front panel will turn red.
The generator is considered loaded when either the AC current is equal to or greater than 5% of full load
current.
The WaveNet incorporates an Advanced Setup menu. Only advanced and knowledgeable users should
change these parameters.
20
The actions in Table 8 should be performed routinely.
WARNING: When performing any WaveNet or Engine maintenance be certain
controller is in OFF mode, is isolated from all possible sources of power,
and the crank wire is removed from the Controller.
Table 8: Recommended Maintenance
PROCEDURE
ACTION
Making the controller safe for inspection
and maintenance.
Disconnect all possible power sources before
controller inspection.
Inspect controller mounting location for
possible safety issues.
Inspect mounting location for any safety or fi re issues.
Inspect for dirt, wiring damage and mechanical damages.
Inspect controller for loose fasteners,
terminals and wiring connections.
Check all hardware including controller wiring,
terminals etc. for any looseness due to vibrations etc.
Clean area around controller.
Periodically inspect and remove any debris/dirt
from within or near the controller.
Check for any overheating due to loose
connections.
Check for any discoloration, melting or blistering
of any wiring or connections
Perform regular testing of controller
Perform regular testing of the controller to
check for proper operation.