Northern Tool And Equipment QCPS?28000 Owner's Manual - page 9
9
VENTING
9. Located terminations: a) not less than 0.91 m (3 ft) above any forced air inlet located within 3.05 m
(10 ft); b) not less than 1.22 m (4 ft) below or horizontally from, or one foot above, any door, window
or gravity air inlet into any building; c) not less than 0.61 m (2 ft) from an adjacent building and not
less than 2.13 m (7 ft) above grade when located adjacent to a public walkway.
VERTICALLY WITH CHIMNEY SYSTEM
1. Follow L‐Vent chimney manufacturer’s instructions.
2. Option – to achieve a centered vertical installation, a 45 degree elbow and a clean‐out tee can be
used to offset the pipe from the exhaust outlet to the rear center of the stove.
3. Option – install L‐vent elbow in place of clean‐out tee. Locate stove. Drop plumb bob to center of
tee outlet, mark point on ceiling. Install ceiling support and L‐vent pipe as per L‐vent manufacturer’s
instructions.
4. Always maintain 76.2mm (3 in) clearance from combustible materials. When passing through
additional floors or ceilings, always install fire‐stop spacer.
5. After liner is up, cut either round or square hole in roof, always 76.2mm (3 in) larger all the way
around pipe. Install upper edge and sides of flashing under roofing materials, nail to the roof along
upper edge. Do not nail lower edge. Seal nail heads with flexible waterproof sealant.
6. Apply flexible, waterproof sealant where the storm collar meets the vent. Slide storm collar down
until it sits on the flashing. Seal and install cap.