Novar EP/2-EA Installation Instructions Manual - page 6
Step
Procedure
4
Use the hex wrench to tighten the retaining screw in the
mounting post on the right side to secure the EP/2 electronics
assembly to the baseplate.
§
The left retaining screw cannot be used with the Ethernet
Adapter installed.
Checking Installation
To check the installation, monitor the five status light-emitting diodes (LEDs) on
the face of the Ethernet Adapter.
§
The Good Link status LED will blink once when power is supplied to the
EP/2. After several seconds it will remain lit, indicating that the network is
correctly wired and configured and working properly.
§
The Polarity status LED, when lit, indicates that the network wiring polarity is
reversed. The adapter will continue to function. Check the Ethernet network
cable wiring and correct the polarity.
§
The Receive and Transmit status LEDs flash on and off intermittently to show
that communication is occurring if the EP/2 is communicating with the LAN.
§
The Collision status LED blinks occasionally during normal communications.
If this LED blinks often or stays on for long periods it indicates a problem.
Monitor the Ethernet network’s operation on the EP/2’s display. Refer to Novar’s
Controls EP/2 Keypad and Display Instructions (Document No. 5601190).
LOGIC ONE
®
IS A REGISTERED TRADEMARK OF NOVAR CONTROLS CORPORATION.
ETHERNET
®
IS A REGISTERED TRADEMARK OF XEROX CORPORATION.
THE CONTENTS OF THIS DOCUMENT ARE SUBJECT TO CHANGE WITHOUT NOTICE.
COPYRIGHT © 2004 BY NOVAR CONTROLS CORPORATION. ALL RIGHTS RESERVED.
PRINTED IN THE U.S.A.
NOVAR CONTROLS CORPORATION
6060 ROCKSIDE WOODS BLVD., CLEVELAND, OH 44131
TEL.: 800.348.1235
WWW.NOVARCONTROLS.COM
4
Doc. #569040000—A
7/30/04
Ethernet
®
Adapter Installation Instructions