Floor Protector
The stove may be installed on a combustible fl oor provided
noncombustible ember protection is used.
This protection must extend as follows:
In Canada: 18" (457 mm) on the fi ring side and 8" (203 mm) to the
other sides. See Figure #4, below.
Combustion Air
Intake or combustion air can be supplied to the stove in one of
two ways. Consult your local building code or CAN/CSA-B365,
Installation Code for Solid-Fuel-Burning Appliances and Equipment
before proceeding.
1. Outside air supply - (Necessary for mobile home installation,
optional for residential installation.) Outside air may be drawn
from either underneath the stove or from behind.
To draw outside air through the fl oor, leave the 4" knockout or
cover plate in place in the rear of the pedestal or leg kit ash box
enclosure.
Pedestal
Model: Cut or drill a 4" diameter hole in the fl oor
anywhere inside the perimeter of the pedestal. Cover the hole
with a 4" x 4" (100 mm x 100 mm) rodent screen and staple/nail
in place.
Leg
Model: Cut or drill a 4" diameter hole directly below the
bottom hole of the ash box enclosure. Connect enclosure to
the fl oor with a short 4" diameter pipe. If you wish to connect
the outside air to the rear hole on the ash box, then remove the
4" knockout or cover plate at the rear of the ash box.
This hole must get its air from a ventilated crawl space or be
extended with duct to the outdoors (see Figure #3, Page 7). The
use of outside combustion air for residential installation requires
the unit to be secured to the structure to prevent dislodging of
the air duct.
To draw outside air from behind the stove, an outside air adaptor
may be required (see Optional Blower section). Cut or drill
a 4" hole through a wall behind the unit. Use an appropriate
household 4" inlet. You must remove the rear cover plate from
the pedestal or move the cover plate at the rear of the leg kit
ash box enclosure to cover the bottom hole.
Note:
This unit is not designed to be operated with the fi ring door
open. In addition to the obvious hazard of sparks landing on
combustibles, an open fi re door will cause the heater to draw
air from the living space and possibly cause suffocation.
2. Room air supply - Remove the cover plate from the rear of the
pedestal or leg kit ash box enclosure. The stove will now draw
its air from the room through this opening and into the fi rebox
intake.
Note:
The living space around the heater must be well ventilated
with good air circulation. Anything that may cause a negative
pressure can cause gases or fumes to be pulled into the living
area. During extremely cold weather, and especially when burning
at very slow rates, the upper parts of the exposed chimney may
ice up, partially blocking the fl ue gases. If blockage occurs, fl ue
gases may enter living space.
U.S.A. Only
Non-combustible
fl oor protector
FIG. #4
FIG. #5
In USA: 16" (406 mm) to the front and 8" (203 mm) to the sides
of the fuel loading door opening. See Figure #5, below. This
protection is also required under the chimney connector and 2" (51
mm) beyond each side.
Minimum Width - 41 1/2"
Minimum Overall Depth - 51 1/8"
Non-combustible
fl oor protector
Minimum Width - 36"
Minimum Overall Depth - 40 1/2"
8" [203mm]
18" [457mm]
8" [203mm]
8" [203mm]
16" [406mm]
8" [203mm]
8" [203mm]