Panasonic CS-E24DKE Service Manual - page 35
8.2.2.3. Anti-Freezing Control
1. When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.
3. At the same time, indoor fan speed increase +40 rpm compared to its normal operation.
4. If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.
8.2.2.4. Anti-Dew Formation Control
a) Control 1
This control is perform if the following conditions is fulfilled during cooling/dry operation.
i. Control Start Condition
1) Indoor Intake Temperature
24°C & above
2) Outdoor Temperature
Refer below
3) Remote Control Setting Temperature
16°C & above, below 30°C
4) Fan tab
Refer below
Control start after 1) ~ 4) continued for more than 1 minutes.
ii. Control Contents
* If the outdoor temperature
30°C
Me & above (include auto air flow)
0
T
74
30 min
T
67
90 min
T
67
0
T
67
30 min
T
54
90 min
T
54
35
CS-E24DKE CU-E24DKE