Panasonic CS-E24DKE Service Manual - page 36
* If the outdoor temperature
Me & above (include auto air flow)
0
T
74
30 min
T
67
90 min
T
67
0
T
67
30 min
T
54
90 min
T
47
b) Control 2
•
When the following conditions occurs for 20 minutes continuously, anti-dew formation is controlled and air vane change
Horizontal vane shift to 2nd position and Vertical vane shift to center position.
1. Indoor intake air temperature is 25°C or above and less than 29°C.
2. Outdoor air temperature is less than 30°C.
3. Air vane control: Manual Horizontal Airflow and Manual Vertical Airflow.
4. Fan speed is quiet Lo.
8.2.3. Protection Control For Heating Operation
8.2.3.1.
Anti Cold Draft Control
Indoor fan speed varies in accordance to indoor heat exchanger temperature, based on type of air volume and direction, as shown
below.
1. Manual Fan Speed
36
CS-E24DKE CU-E24DKE