Raypak B6000 Installation And Operating Manual - page 22
22
30049
40049
bit Boiler #6 Status Word
Boiler #6
R
10289
0
Boiler Not On Line
(0 = Normal, 1 = Alarm)
R
10290
1
Boiler Operation
(0 = Firing, 1 = Ready)
R
10291
2
Low Water Cutoff
(0 = Normal, 1 = Alarm)
R
10292
3
Low Pressure Water
(0 = Normal, 1 = Alarm)
R
10293
4
Low Pressure Gas
(0 = Normal, 1 = Alarm)
R
10294
5
High Pressure Gas
(0 = Normal, 1 = Alarm)
R
10295
6
High Limit
(0 = Normal, 1 = Alarm)
R
10296
7
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R
10297
8
Manual Override
(0 = Normal, 1 = Alarm)
R
10298
9
Flow Switch
(0 = Normal, 1 = Alarm)
R
10299
10 No Pilot
(0 = Normal, 1 = Alarm)
30050
40050
bit Boiler #7 Status Ward
Boiler #7
R
10305
0
Boiler Not On Line
(0 = Normal, 1 = Alarm)
R
10306
1
Boiler Operation
(0 = Firing, 1 = Ready)
R
10307
2
Low Water Cutoff
(0 = Normal, 1 = Alarm)
R
10308
3
Low Pressure Water
(0 = Normal, 1 = Alarm)
R
10309
4
Low Pressure Gas
(0 = Normal, 1 = Alarm)
R
10310
5
High Pressure Gas
(0 = Normal, 1 = Alarm)
R
10311
6
High Limit
(0 = Normal, 1 = Alarm)
R
10312
7
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R
10313
8
Manual Override
(0 = Normal, 1 = Alarm)
R
10314
9
Flow Switch
(0 = Normal, 1 = Alarm)
R
10315
10 No Pilot
(0 = Normal, 1 = Alarm)
30035
40051
bit Boiler #3 Status Ward
Boiler #8
R
10321
0
Boiler Not On Line
(0 = Normal, 1 = Alarm)
R
10322
1
Boiler Operation
(0 = Firing, 1 = Ready)
R
10323
2
Low Water Cutoff
(0 = Normal, 1 = Alarm)
R
10324
3
Low Pressure Water
(0 = Normal, 1 = Alarm)
R
10325
4
Low Pressure Gas
(0 = Normal, 1 = Alarm)
R
10326
5
High Pressure Gas
(0 = Normal, 1 = Alarm)
R
10327
6
High Limit
(0 = Normal, 1 = Alarm)
R
10328
7
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R
10329
8
Manual Override
(0 = Normal, 1 = Alarm)
R
10330
9
Flow Switch
(0 = Normal, 1 = Alarm)
R
10331
10 No Pilot
(0 = Normal, 1 = Alarm)
R
30052
40052
Setpoint
Day Setpoint (Desired water temp @70F)
R
30053
40053
Nitesetback Night Setback (Desired water temp @ 70F)
R
30054
40054
Ratio Out
1-200 = 0.1 - 20.0 in 0.1 increments
R
30055
40055
Throttling
Delta T of all boilers in system (Normally 20 / # boilers)
R
30056
40056
Modulating Step (%) min 5% steps
R
30057
40057
Wait State Time (Sec)
R
30058
40058
Outdoor Cut off Temperature (O/C)
R
30059
40059
Control Band (degrees F Tolerance from TAR) (C/B)
R
30060
40060
Lead Boiler Number (1 to Number of Boilers)
R
30061
40061
Number of Boilers
R
30062
40062
TP - Boiler Pump Delays (Min) Boiler #1
R
30063
40063
TP - Boiler Pump Delays (Min) Boiler #2
R
30064
40064
TP - Boiler Pump Delays (Min) Boiler #3
R
30065
40065
TP - Boiler Pump Delays (Min) Boiler #4
R
30066
40066
TP - Boiler Pump Delays (Min) Boiler #5
R
30067
40067
TP - Boiler Pump Delays (Min) Boiler #6
R
30068
40068
TP - Boiler Pump Delays (Min) Boiler #7
R
30069
40069
TP - Boiler Pump Delays (Min) Boiler #8
A-4