Rittal PMC 12 Assembly And Operation Instructions Manual

Other manuals for PMC 12: Oweners manual, User Manual, Instruction Manual
Manual is about: Power Modular Concept

Summary of PMC 12

  • Page 1

    Assembly and operation instructions ups system power modular concept pmc 12 1, 2 and 3kva pmc12 compact 2 and 3kva 7857.430 7857.431 7857.432 7857.482 7857.483.

  • Page 2

    Microsoft windows is a registered trademark of microsoft corporation. Acrobat reader is a registered trademark of adobe systems incorporated..

  • Page 3: Important Safety Instruction

    Important safety instruction ups-manual 2 en table of contents 1. Important safety instruction 3 1.1. D ocumentation n otes ........................... 3 1.2. R etention of the d ocuments ................ 3 1.3. U sed s ymbols ......................................... 3 1.4. S afety i nstructions .....

  • Page 4: Important Safety Instruction

    Important safety instruction ups-manual 3 en 1. Important safety instruction 1.1. Documentation notes the audience for this guide is the technical specialist familiar with the assembly, installation and operation of the pmc12 ups-system. You should read this operating guide prior to commissioning an...

  • Page 5: Important Safety Instruction

    Important safety instruction ups-manual 4 en 13. Always switch off the ups and discon- nect the batteries when relocating the ups. 14. It should be recharged every 2-3 months if unused. If this is not done, then the warranty will be null and void. When installed and being used, the batteries will be...

  • Page 6: Product Introduction

    Product introduction ups-manual 5 en 2. Product introduction 2.1. General characteristics true online technology continuously supplies your critical device with stable, regulated, tran- sient-free pure sine wave ac power. 1. High-efficiency 20 khz pwm sine-wave to- pology yields an excellent overall...

  • Page 7: Ups Functional Descriptions

    Ups functional descriptions ups-manual 6 en 3. Ups functional descriptions 3.1. Ups front panel display ① lcd display ② green led steadily lights up to indicate that the utility input voltage is within the window (160vac~288vac). ③ , ④ green led lights up to indicate there is an output available at ...

  • Page 8: Ups Functional Descriptions

    Ups functional descriptions ups-manual 7 en 230v 1kva 2kva 3kva 3.2. Rear panel description pmc12 1. Usb port 2. Rs232 port 3. Emergency power off (epo) dry contact signal inputs 4. Communication card options slot 5. External battery connector 6. Ac power connection socket 7. Ac outlets 8. Two progr...

  • Page 9: Ups Functional Descriptions

    Ups functional descriptions ups-manual 8 en 3.3. Rear panel description pmc12 compact 1. Usb port 2. Rs232 port 3. Emergency power off (epo) dry contact signal inputs 4. Communication card options slot 5. External battery connector 6. Ac power connection socket 7. Ac outlets 8. Two programmable outl...

  • Page 10: Ups Functional Descriptions

    Ups functional descriptions ups-manual 9 en 3.4. Operating modes & ups configuration install the “rittal pmc12 ups-software“ from the enclosed cd or download it from http://www.Rimatrix5.Com/service_support/downloads.Asp . Run the programm „upsman configuration“. The following window appears: 3.4.1....

  • Page 11: Ups Functional Descriptions

    Ups functional descriptions ups-manual 10 en 1. Turn outlet on after ups is on – select the time to automatically enable this outlet within the specified time when the ups is powered on. If “0” sec is selected, the outlet will be enabled once the ups is powered on. 2. Turn outlet off after ac failur...

  • Page 12: Installation and Operation

    Installation and operation ups-manual 11 en 3.5.1. True rs232 port descriptions the rs232 interface shall be set as follows: baud rate 2400 bps data length 8 bits stop bit 1 bit parity none the pin assignments of the true rs232 port are illustrated as follows: • to be continually supplied via bypass...

  • Page 13: Installation and Operation

    Installation and operation ups-manual 12 en 5. This ups is not designed for outdoor use. Note! The recommended temperature range for the batteries is between 20 and 30°c. Is the ups running permanent in an environment with temperatures over 40°c this will lead to a clear shortened life-time of the b...

  • Page 14: Installation and Operation

    Installation and operation ups-manual 13 en 4.3.3. Rack-mount configuration setup step 1 step 2 step 3 step 4.

  • Page 15: Installation and Operation

    Installation and operation ups-manual 14 en 4.4. Operation 4.4.1. Start up in normal mode 1. Make sure the voltage of utility matches with the input voltage window of the ups. 2. Connect the ups to the wall receptacle of the utility. Turn on the ups “on” switch to start up the ups. Led (nr. 2) and (...

  • Page 16: Installation and Operation

    Installation and operation ups-manual 15 en must be completely restarted to get back to normal mode. Drawing h 4.4.3. Check measured values & figures detected by ups if you would like to check the measured values & messages, please use scroll up and scroll down key pads. When you use scroll down key...

  • Page 17: Installation and Operation

    Installation and operation ups-manual 16 en frequency synchronized window) Ædrawing t (inverter output voltage) Ædrawing u1(ups operation mode) Ædrawing v(output voltage fine tuning). Drawing q1 drawing q2 drawing r1 drawing r2 drawing s drawing t drawing u1 drawing u2 drawing u3 drawing v.

  • Page 18: Installation and Operation

    Installation and operation ups-manual 17 en 3. Press scroll up key pad, you may exe- cute special functions. The functions include buzzer on (as drawing q1) or buzzer off (as drawing q2, alarm silence for ups warning) and self-test off (as drawing q2). Ups will execute battery test for 10 seconds, i...

  • Page 19: Installation and Operation

    Installation and operation ups-manual 18 en (b) check to see chapter 6.1 to trouble shoot the problem of the ups; otherwise, consult your local distributor for service. (c) press key pad for 5 seconds and buzzer will sound twice. (d) turn off the breaker of the utility input. (e) the ups lock proble...

  • Page 20: Installation and Operation

    Installation and operation ups-manual 19 en 4.6. Battery replacement pmc12 step 1 step 2 step 3 note! Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions. When replacing batteries, replace with the same type and number of batte...

  • Page 21: Installation and Operation

    Installation and operation ups-manual 20 en 4.7. Battery replacement pmc12 compact step 1: step 2: step 3: step 4: note! Was the used battery of the ups system removed during normal operation this will not immediately be recognized by the pmc12 because after the startup the ups will check only spora...

  • Page 22: Ups Working Principle

    Ups working principle ups-manual 21 en 5. Ups working principle 5.1. Ups system block diagram fig 5.1 figure 5.1 above illustrates the true on-line double conversion architecture of the ups system. The major modules consist of: 1. An ac to dc power converter (rectifier) with pfc control circuit 2. A...

  • Page 23: Ups Working Principle

    Ups working principle ups-manual 22 en 5.3. When mains is absent the working principle of the ups under mains absent condition is illustrated as follows: 1. When mains absent, the ups will direct the battery energy automatically to the inverter without delay, and turn off the charger and ac/dc conve...

  • Page 24: Maintenance Guide

    Maintenance guide ups-manual 23 en 5.5.2. Inverter/internal over temperature if the ups experiences internal over-tempera- ture when utility is normal, it will switch to by- pass loop. The ups will switch back to inverter mode when the over-temperature situation is eliminated. If over temperature oc...

  • Page 25: Maintenance Guide

    Maintenance guide ups-manual 24 en situation check items solution ups fails to provide battery backup or its back up time is shorter than its intended performance. If the backup time remains non- satisfactory after 8 hours of charging, please contact your local dealer for battery replacement. Ups is...

  • Page 26: Bundle Software Installation

    Bundle software installation ups-manual 25 en 6.2. Error codes and their descriptions code descriptions er05 battery weak or faulty er06 output short-circuited er07 epo mode er11 ups over-temperature er12 inverter overload er14 fans out of order er18 eeprom's data error er24 utility low ( battery di...

  • Page 27: Optional Communication Card

    Optional communication card ups-manual 26 en 8. Optional communication card the simple network management protocol (snmp) is a worldwide-standardized communi- cation-protocol. It is used to monitor any device in the network via simple control language. The ups-management software also provides its d...

  • Page 28: Technical Specifications

    Technical specifications ups-manual 27 en 10. Technical specifications model 1kva 2kva 3kva va rating apparent output power 1000va 2000va 3000va active output power 800 watts 1600 watts 2400 watts power factor 0,8 topology double conversion on-line type rack/tower agency approvals 230v models: ce in...

  • Page 29: Technical Specifications

    Technical specifications ups-manual 28 en harmonic distortion 3% thd(linear load) 7% thd(non-linear load) transient response(ms) 60ms/5% efficiency waveform pure sine wave to ac mode (full load) 88% 88% 90% efficiency to battery mode (full load) 85% 85% 87% model 1kva 2kva 3kva battery system type 1...

  • Page 30: Technical Specifications

    Technical specifications ups-manual 29 en protection (ac mode ) >106% ~ 120% for 30 seconds transfer to bypass >121% ~ 150% for 10 seconds transfer to bypass >150% for immediately transfer to bypass buzzer continuously alarms. (battery mode) >106% ~ 120% for 30 seconds shuts down >121% ~ 150% for 10...

  • Page 31: Technical Specifications

    Technical specifications ups-manual 30 en environmental operation temperature* 0 - 40 °c noise level relative humidity 0 to 90% (without condensation) interface interface type 1x usb port, 1x rs-232 port, 1x slot for communication card snmp power management from snmp manager and web browser compatib...

  • Page 32: Technical Specifications

    Technical specifications ups-manual 31 en this side is intentionally empty..

  • Page 33