Rittal PMC 12 Oweners manual

Manual is about: Power Modular Concept

Summary of PMC 12

  • Page 1

    Rittal pmc12 ups-manual 7857.430 7857.431 7857.432 1phase double conversion true online ups system 1 - 3kva f r i d h e l m l o h g r o u p r i t t a l gmbh & co. Kg auf dem stützelberg d – 3 5 7 4 5 h e r b o r n deutschland germany email: info@rittal.De http://www.Rittal.Com service -tel. : (+49) ...

  • Page 2

    Important safety instruction ups-manual 2 en microsoft windows is a registered trademark of microsoft corporation. Acrobat reader is a registered trademark of adobe systems incorporated..

  • Page 3

    Important safety instruction ups-manual 3 en table of contents 1. Important safety instruction .............................................. 4 1.1. D ocumentation n otes ........................... 4 1.2. R etention of the d ocuments ................ 4 1.3. U sed s ymbols .............................

  • Page 4

    Important safety instruction ups-manual 4 en 1. Important safety instruction 1.1. Documentation notes the audience for this guide is the technical specialists familiar with the assembly, installa- tion and operation of the pmc12 ups-system. You should read this operating guide prior to the commissio...

  • Page 5

    Important safety instruction ups-manual 5 en 15. Observe the valid regulations for the electrical installation for the country in which the unit is installed and operated, and the national regulations for accident prevention. Also observe any company- internal regulations (work, operating and safety...

  • Page 6: Product Introduction

    Product introduction ups-manual 6 en 2. Product introduction 2.1. General characteristics true online technology continuously supplies your critical device with a stable, regulated, transient-free pure sine wave ac power. 1. High-efficiency pwm sine-wave topology yields an excellent overall performa...

  • Page 7

    Ups functional descriptions ups-manual 7 en 3. Ups functional descriptions 3.1. Ups front panel display ① lcd display ② green led steadily lights up to indicate that the utility input voltage is within the window (160vac~288vac). ③ , ④ green led lights up to indicate there is an output available at ...

  • Page 8: 230V

    Ups functional descriptions ups-manual 8 en 230v 1kva 2kva 3kva 3.2. Rear panel descriptions 1. Usb port 2. Rs232 port 3. Emergency power off (epo) dry contact signal inputs 4. Communication card options slot 5. External battery connector 6. Ac power connection socket 7. Ac outlets 8. Two programmab...

  • Page 9

    Ups functional descriptions ups-manual 9 en 3.3. Operating modes & voltage system configurations download from www.Rimatrix5.Com/dl_power.Htm the “setting tool” and open the software to see the screen as below: 3.3.1. System configuration settings 1. System voltage selection: select input voltage 22...

  • Page 10

    Ups functional descriptions ups-manual 10 en 4. Outlet turn off when battery lower than - select this option to automatically disable the outlet at the specified remaining battery power capacity(%) during battery mode to shed the less critical loads to prolong battery back-up time for the other more...

  • Page 11: Installation And Operation

    Installation and operation ups-manual 11 en 4. Installation and operation warning! Read the safety instruction guide (page 5 to 6) before installing the ups! 4.1. Unpacking inspect the ups upon receipt. The manufac- turer designed robust packaging for your prod- uct. However, accidents and damage ma...

  • Page 12: Installation And Operation

    Installation and operation ups-manual 12 en 4.3.2. Power module + battery module step 1 step 2 4.3.3. Rack-mount configuration setup step 1 step 2 step 3 step 4.

  • Page 13: Installation And Operation

    Installation and operation ups-manual 13 en 4.4. Operation 4.4.1. Start up in normal mode 1. Make sure the voltage of utility matches with the input voltage window of the ups. 2. Connect the ups to the wall receptacle of the utility. Turn on the ups “on” switch to start up the ups. Led (nr. 2) and (...

  • Page 14: Installation And Operation

    Installation and operation ups-manual 14 en drawing h drawing i 4.4.3. Check measured values & figures detected by ups if you would like to check the measured values & messages, please use scroll up and scroll down key pads. When you use scroll down key pad, the lcd display will illustrate in se- qu...

  • Page 15: Installation And Operation

    Installation and operation ups-manual 15 en drawing p2 2. Press key pad to scroll down the lcd screen, then check the ups settings. The lcd display will show in sequence: drawing p1(buzzer)drawing q1(self test)drawing r1(bypass voltage)drawing s(output fre- quency synchronized window)drawing t (inve...

  • Page 16: Installation And Operation

    Installation and operation ups-manual 16 en 3. Press scroll up key pad, you may exe- cute special functions. The functions include buzzer on (as drawing q1) or buzzer off (as drawing q2, alarm silence for ups warning) and self-test off (as drawing r2). Ups will execute battery test for 10 seconds, i...

  • Page 17: Installation And Operation

    Installation and operation ups-manual 17 en (d) turn off the breaker of the utility input. (e) the ups lock problem is solved now. 4.4.7. Shut off 1. Press key pad for about 5 seconds, the inverter output will be turned off, then the output load is supplied by bypass loop and the lcd screen shows as...

  • Page 18: Ups Working Principle

    Ups working principle ups-manual 18 en step 4 1kva 2k/3kva 5. Ups working principle 5.1. Ups system block diagram fig 5.1 figure 5.1 above illustrates the true on-line double conversion architecture of the ups system. The major modules consist of: 1. An ac to dc power converter (rectifier) with pfc ...

  • Page 19: Ups Working Principle

    Ups working principle ups-manual 19 en fig 5.5 5.3. When mains is absent the working principle of the ups under mains absent condition is illustrated as follows: 1. When mains absent, the ups will direct the battery energy automatically to the inverter without delay, and turn off the charger and ac/...

  • Page 20: Maintenance Guide

    Maintenance guide ups-manual 20 en 5.5.2. Inverter/internal over temperature if the ups experiences internal over-tempera- ture when utility is normal, it will switch to by- pass loop. The ups will switch back to inverter mode when the over-temperature situation is eliminated. If over temperature oc...

  • Page 21: Maintenance Guide

    Maintenance guide ups-manual 21 en situation check items solution ups fails to provide battery backup or its back up time is shorter than its intended performance. If the backup time remains non-satisfactory after 8 hours of charging, please contact your local dealer for battery replacement. Ups is ...

  • Page 22

    Bundle software installation guide ups-manual 22 en 7. Bundle software installation guide 7.1. Hardware installation 1. Connect the male connector of rs232/usb cable to the ups communication port. 2. Connect the female connector of the rs232/usb cable to a dedicated rs232 port of the computer. 3. Fo...

  • Page 23: Customer Service

    Customer service ups-manual 23 en erating systems, analogous to pmc-software. Our snmp interfaces are compatible to rccmd. 9. Customer service if you have any technical questions or ques- tions concerning our product spectrum, contact the following service address: tel.: +49 (0)2772/505-1855 http://...

  • Page 24: Technical Informations

    Technical informations ups-manual 24 en 10. Technical informations model 1kva 2kva 3kva va rating apparent output power 1000va 2000va 3000va active output power 700watts 1400watts 2100watts power factor 0,7 topology double conversion on-line type rack/tower agency approvals 230v models: ce input vol...

  • Page 25: Technical Informations

    Technical informations ups-manual 25 en model 1kva 2kva 3kva battery system type 12v/7,2ah 12v/7,2ah 12v/9ah numbers of batteries 3 6 6 backup time(20%) >66min. >66min. >59min. Backup time(40%) >27min. >28min. >19min. Backup time(60%) >14min. >14min. >12min. Backup time(80%) >10min. >10min. >8min. B...

  • Page 26: Technical Informations

    Technical informations ups-manual 26 en model 1kva 2kva 3kva (bypass mode) >106% ~ 120% for 250 seconds shuts down > 121% ~ 130% for 125 seconds shuts down >131% ~ 135% for 50 seconds shuts down >136% ~ 145% for 20 seconds shuts down >146% ~ 148% for 5 seconds shuts down >149% ~ 157% for 2 seconds s...

  • Page 27: Technical Informations

    Technical informations ups-manual 27 en model 1kva 2kva 3kva backup time with extended battery module load 100% >66min. >34min. >30min. 80% >90min. >52min. >46min. 60% >120min. >69min. >60min. 40% >180min. >109min. >95min. 1 extended battery module 20% >350min. >210min. >180min. Load 100% >130min. >...

  • Page 28: Technical Informations

    Technical informations ups-manual 28 en.