RKC INSTRUMENT CB100 Initial Setup Manual

Other manuals for CB100: Communication Instruction Manual
Manual is about: Digital Controller

Summary of CB100

  • Page 1

    Imcb04-e9 rkc instrument inc. ® digital controller cb100/cb400 cb500/cb700 cb900 initial setting manual.

  • Page 2

    All rights reserved, copyright 1998, rkc instrument inc..

  • Page 3: Symbols

    Imcb04-e9 i-1 thank you for purchasing the rkc instrument. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference. Symbols : this mark indicat...

  • Page 4: Notice

    Imcb04-e9 i-2 ! This is a class a instrument. In a domestic environment, this instrument may cause radio interference, in which case the user may be required to take adequate measures. ! This instrument is protected from electric shock by reinforced insulation. Provide reinforced insulation between ...

  • Page 5: Contents

    Imcb04-e9 i-3 contents page 1. Transfer to mode .......................................................... 1 1.1 transfer to initialization mode .........................................................................1 1.2 end of initialization mode ....................................................

  • Page 6: Memo

    I-4 imcb04-e9 memo.

  • Page 7: 1. Transfer to Mode

    Imcb04-e9 1 1. Transfer to mode initialization is to set parameters relating to instrument specifications (input type, input range, alarm type, etc.) and those relating to instrument characteristics (setting limiter, alarm differential gap, etc.). 1.1 transfer to initialization mode 1. Turn on the p...

  • Page 8

    1. Transfer to mode imcb04-e9 2 6. Press the set key to change to the next parameter. Thus, the data in initialization mode is unlocked. The parameter to be displayed varies depending on the specification. 7. Press the initialization mode. Thus, the symbol (cod) for selecting the initialize code is ...

  • Page 9

    1. Transfer to mode imcb04-e9 3 1.2 end of initialization mode if the setting is changed, always check all of the set values (sv setting mode, parameter setting mode). 1. After each parameter is set, keep pressing the key to change the present mode to the pv/sv display mode. 2. Press the set key for...

  • Page 10: 2. Setting

    4 imcb04-e9 2. Setting 2.1 display flowcharts in initialization mode if the instrument is changed to initialization mode, the symbol (cod) for selecting the initialize code is displayed first. Initializing items are classified into 3 initialize code groups in initialization mode. There are parameter...

  • Page 11

    2. Setting imcb04-e9 5 2.2 procedure for setting each parameter [example of changing the setting] when the display unit shows sl1 (input type selection) in initialize code 0, the following procedure is for changing the input type from k to j. 1. Change the instrument to the initialize code selection...

  • Page 12

    2. Setting imcb04-e9 6 3. Press the up key to enter 1 in the units digit of the set value (sv) display unit. 4. Press the set key to change to the next parameter. Thus, the set value is registered. If the initialize code is set to 1 or 2, enter 1 or 2 in the units digits of the set value (sv) displa...

  • Page 13

    2. Setting imcb04-e9 7 2.3 list of parameters in initialize code 0 (cod = 0) (1) sl1 (input type selection) conduct the setting so that it matches the instrument specification (input type). If the setting is changed, always check all of the set values (sv setting mode, parameter setting mode). Facto...

  • Page 14

    2. Setting imcb04-e9 8 (2) sl2 (engineering unit selection and cooling type selection) the upper 2 digits are not used. Do not change the setting, as this may cause malfunction. Factory set value varies depending on the instrument specification. Set value description 0 ° c engineering unit selection...

  • Page 15

    2. Setting imcb04-e9 9 (3) sl3 (heater break alarm [hba], control loop break alarm [lba], special specification, or control loop break alarm [lba] output selection ) cannot be used the heater break alarm (hba) for the following instruments. • instrument without the second alarm (alm2) output. • inst...

  • Page 16

    2. Setting imcb04-e9 10 (4) sl4 (first alarm [alm1] type selection, hold action selection) the following instrument is set to 0000. • instrument without the first alarm (alm1) output. • instrument of the sv alarm or control loop break alarm (lba) is used as the first alarm (alm1). Factory set value ...

  • Page 17

    2. Setting imcb04-e9 11 (6) sl6 (control action type selection) conduct setting so as to meet the instrument specification. An incorrect setting may cause a malfunction. When control action is of the type d or f, control action type selection (cool-side) setting is ignored. Factory set value varies ...

  • Page 18

    2. Setting imcb04-e9 12 (7) sl7 (energized/de-energized selection, special specification selection 1) the following instrument is set to 0000. Instrument without both the first alarm (alm1) output and the second alarm (alm2) output. Factory set value varies depending on the instrument specification....

  • Page 19

    2. Setting imcb04-e9 13 (9) sl9 (special specification selection 3) any item set in the z-168 specification has priority over that set in sl3 (heater break alarm selection). Factory set value varies depending on the instrument specification. Set value description 0 z-168 specification not provided *...

  • Page 20

    2. Setting imcb04-e9 14 (11) sl11 (sv alarm type selection) the following instrument always set it to 0 : first alarm, sv alarm not provided. • instrument without the first alarm (alm1) output. • instrument of the process alarm, deviation alarm, band alarm or control loop break alarm (lba) is used a...

  • Page 21

    2. Setting imcb04-e9 15 2.4 list of parameters in initialize code 1 (cod = 1) (1) slh (setting limiter [high limit]) set the limiter by referring to input range table (p.17) " " " " setting method press the up or down key. The set value (sv) display shows the numeric value. Factory set value varies ...

  • Page 22

    2. Setting imcb04-e9 16 (2) sll (setting limiter [low limit]) set the limiter by referring to input range table (p.17) " " " " setting method press the up or down key. The set value (sv) display shows the numeric value. Factory set value varies depending on the instrument specification. Input type s...

  • Page 23

    2. Setting imcb04-e9 17 " " " " input range table thermocouple input (tc) type input range type input range k 0 to 200 ° c b 400 to 1800 ° c *3 k 0 to 400 ° c b 0 to 1820 ° c *1,*3 k 0 to 600 ° c b 800 to 3200 ° f *3 k 0 to 800 ° c b 0 to 3308 ° f *1,*3 k 0 to 1000 ° c e 0 to 800 ° c k 0 to 1200 ° c...

  • Page 24

    2. Setting imcb04-e9 18 type input range l 0 to 400 ° c l 0 to 800 ° c l 0 to 800 ° f l 0 to 1600 ° f *1 accuracy is not guaranteed between 0 to 399 ° c (0 to 799 ° f). *2 accuracy is not guaranteed between -199.9 to -100.0 ° c (-199.9 to -158.0 ° f). *3 can’t be selected for the instrument with the...

  • Page 25

    2. Setting imcb04-e9 19 voltage input type input range 0 to 5 v dc 0.0 to 100.0 % 0 to 10 v dc * 1 to 5 v dc * for the 0 to 10 v dc (z-1010 specification), no input type cannot be changed as the hardware differs. Current input type input range 0 to 20 ma dc 4 to 20 ma dc 0.0 to 100.0 % for the curre...

  • Page 26

    2. Setting imcb04-e9 20 (3) pgdp (decimal point position setting) any digits other than the units digit are not used. As malfunction may result, do not change any of these digits. The decimal point position setting is displayed only for voltage or current input. Factory set value: 0001 set value des...

  • Page 27

    2. Setting imcb04-e9 21 (6) ah2 (second alarm [alm2] differential gap setting) * setting range tc and rtd inputs: 0 to 100 ° c [ ° f] or 0.0 to 100.0 ° c [ ° f] voltage and current inputs: 0.0 to 10.0 % of span factory set value tc and rtd inputs: 2 ° c [ ° f] or 2.0 ° c [ ° f] voltage and current i...

  • Page 28

    2. Setting imcb04-e9 22 (10) stpk (factor to calculate proportional band) * as this factor is so adjusted that the self-tuning result optimum to most controlled-objects is obtained, do not change it. This is the factor to adjust the proportional band to be calculated by the self-tuning function. The...

  • Page 29

    2. Setting imcb04-e9 23 2.5 list of parameters in initialize code 2 (cod = 2) parameters in initialize code 2 are only displayed. (1) tcj (holding peak ambient temperature) the maximum ambient temperature on the rear terminal board of the instrument is stored and displayed on the set value (sv) disp...

  • Page 30

    24 imcb04-e9 3. Communication initial identifier ! ! ! ! List of communication initialize identifiers note that there are identifiers which cannot be communicated depending on the specification. For details on the structure of communication data, see the instruction manual for cb100/cb400/cb500/cb70...

  • Page 31

    3. Communication initial identifier imcb04-e9 25 id: identifier (ro: read only r/w: read/write) name id data range factory set value r/w control action type selection [sl6] ca 0 to 15 see *3 to vary depending on the specification r/w energized/de-energized alarm selection, special specification sele...

  • Page 32

    3. Communication initial identifier imcb04-e9 26 id: identifier (ro: read only r/w: read/write) name id data range factory set value r/w time factor assumed to be safe [sttm] gh 0 to 200 100 r/w factor to calculate proportional band [stpk] pu 0 to 200 67 r/w factor to calculate integral time[stik] i...

  • Page 33

    3. Communication initial identifier imcb04-e9 27 * 2 0: no alarm 7: process low alarm 1: deviation high alarm 9: deviation high alarm with hold action 2: deviation high/low alarm 10: deviation high/low alarm with hold action 3: process high alarm 11: process high alarm with hold action 5: deviation ...

  • Page 34

    3. Communication initial identifier imcb04-e9 28 9: first alarm (de-energized alarm), second alarm (energized alarm, z-124 specification provided) 10: first alarm (energized alarm), second alarm (de-energized alarm, z-124 specification provided) 11: first alarm (de-energized alarm), second alarm (de...

  • Page 35

    3. Communication initial identifier imcb04-e9 29 *6 0: no option function provided (no optional function provided) 1: run/stop function provided 4: communication function provided (rkc standard communication) 5: communication function provided (rkc standard communication), run/stop function provided...

  • Page 36: Memo

    30 imcb04-e9 memo.

  • Page 37

    The first edition: mar.1998 the ninth edition: sep.2001.

  • Page 38: Imcb04-E9

    Imcb04-e9 sep. 2001 rkc instrument inc. Headquarters: 16-6, kugahara 5-chome, ohta-ku tokyo 146-8515 japan phone: 03-3751-9799 (+81 3 3751 9799) e-mail: info@rkcinst.Co.Jp fax: 03-3751-8585 (+81 3 3751 8585).