RKC INSTRUMENT CB100 Initial Setup Manual - page 33
3. COMMUNICATION INITIAL IDENTIFIER
IMCB04-E9
27
*
2 0: No alarm
7: Process low alarm
1: Deviation high alarm
9: Deviation high alarm with hold action
2: Deviation high/low alarm
10: Deviation high/low alarm with hold action
3: Process high alarm
11: Process high alarm with hold action
5: Deviation low alarm
13: Deviation low alarm with hold action
6: Band alarm
15: Process low alarm with hold action
Do not set 4, 8, 12 or 14. Malfunction may result.
*3 0:
PID action with autotuning (Direct action), time proportioning output (relay contact output,
voltage pulse output, trigger (for triac driving) output or triac output.
1:
PID action with autotuning (Reverse action), time proportioning output (relay contact output,
voltage pulse output, trigger (for triac driving) output or triac output.
3:
Heat/cool PID action with autotuning, heat-side time proportioning output (relay contact
output, voltage pulse output or triac output) or cool-side time proportioning output (relay
contact output, voltage pulse output, triac output).
4:
PID action with autotuning (Direct action) or current output.
5:
PID action with autotuning (Reverse action) or current output.
7:
Heat/cool PID action with autotuning, heat-side current output or cool-side time
proportioning output (relay contact output, voltage pulse output, triac output).
11: Heat/cool PID action with autotuning, heat-side time proportioning output (relay contact
output, voltage pulse output or triac output) or cool-side current output.
15: Heat/cool PID action with autotuning, heat-side current output or cool-side current output.
Do not set 2, 6, 8, 9, 10, 12, 13 or 14. Malfunction may result.
*4 0:
First alarm (Energized alarm), second alarm (Energized alarm)
1:
First alarm (De-energized alarm), second alarm (Energized alarm)
2:
First alarm (Energized alarm), second alarm (De-energized alarm)
3:
First alarm (De-energized alarm), second alarm (De-energized alarm)
4:
First alarm (Energized alarm, Z-124 specification provided), second alarm (Energized alarm)
5:
First alarm (De-energized alarm, Z-124 specification provided), second alarm (Energized
alarm)
6:
First alarm (Energized alarm, Z-124 specification provided), second alarm (De-energized
alarm)
7:
First alarm (De-energized alarm, Z-124 specification provided), second alarm (De-energized
alarm)
8:
First alarm (Energized alarm), second alarm (Energized alarm, Z-124 specification provided)
Continued on the next page.