2. SETTING
IMCB04-E9
13
(9) SL9 (Special specification selection 3)
Any item set in the Z-168 specification has priority over that set in SL3 (heater break alarm
selection).
Factory set value varies depending on the instrument specification.
Set value
Description
0 Z-168 specification not provided
*1 Special specification selection
1 Z-168 specification provided
*2
0
Z-1018 specification not provided
Display selection when operation
1
Z-1018 specification provided
*3, *4 stops (STOP).
0
Z-1041 specification not provided (CT1)
CT1 input value monitoring selection
1
Z-1041 specification provided (CT1)
*5, *6
0
Z-1041 specification not provided (CT2)
CT2 input value monitoring selection
1
Z-1041 specification provided (CT2)
*5, *6
*1 It becomes the item set in SL3 (heater break alarm selection).
*2 Heater break alarm for three-phase heater.
*3 When operation is changed to the STOP state by RUN/STOP selection, a parameter symbol to
indicate the STOP state is displayed on the SV display.
*4 Can’t be selected for the instrument with the modbus communication specification (Z-1021
specification).
*5 For “Heater break alarm (HBA) provided,” the CT input value is displayed regardless of CT input
value monitoring selection.
*6 Z-1041 specification is exclusive use software. For the instrument other than the Z-1041
specification, always set 0.
(10) SL10 (Option selection)
If the communication protocol is changed, turn the power off once, then turn is on again.
Factory set value varies depending on the instrument specification.
Set value
Description
0 RUN/STOP function not provided
RUN/STOP function selection
1 RUN/STOP function provided
0
RKC standard communication
Communication protocol selection *1
1
MODBUS communication
0
Communication function not provided
Communication function selection
1
Communication function provided
0
Self-tuning not provided
Self-tuning function selection
*2
1
Self-tuning provided
*1 For the hardware with the Z-1021 specification (hardware dedicated to modbus communication),
always set the mode to 1: modbus communication.
*2 For the A or W control action type, there is no self-tuning function (0 : self-tuning not provided).