Salicru SLC ADAPT User Manual

Summary of SLC ADAPT

  • Page 1

    Slc adapt slc cube 3+ slc twin pro slc twin pro 33 slc x-tra make before break manual bypass panel for ups (bm*): user's manual.

  • Page 2

    2 salicru.

  • Page 3

    3 general index 1. Introduction. 1.1. Acknowledgement letter. 2. Information for safety. 2.1. Using this manual. 2.1.1. Conventions and used symbols. 2.2. Additional safety notices. 3. Quality and standard guarantee. 3.1. Declaration of the management. 3.2. Standard. 3.3. Environment. 4. Description...

  • Page 4

    4 salicru salicru 1. Introduction. 1.1. Acknowledgement letter. We would like to thank you in advance for the trust you have placed in us by purchasing this product. Read this instruction manual carefully in order to be familiarized with its contents, because, as much as you know and understand the ...

  • Page 5

    5 2.2. Additional safety notices. • in the point of view of the installation and electrical safety, bypass panels must be considered as transformers or power lines of distribution. • as the equipment has protection against electrical shock of class i, it is essential to install the protective earth ...

  • Page 6

    6 salicru 3. Quality and standard guarantee. 3.1. Declaration of the management. Our target is the client’s satisfaction, therefore this management has decided to establish a quality and environmental policy, by means of installation a quality and environmental management system that becomes us capa...

  • Page 7

    7 4. Description. • the manual bypass is a peripheral option to the ups, which allows selecting the power supply source that feeds the loads, either from the ups or directly from commercial elec- trical mains. If the ups has an isolation transformer at its output or in the static bypass line, the ma...

  • Page 8

    8 salicru 4.2. Product definition. 4.2.1. Nomenclature. 3 bm-cube+-p-40-lbt-2/2 ee602322-1. Ee* particular specifications of the client. 2 first character of the output voltage for single phase or phase to phase voltage for three phase. Omit for 230v or 3x400v. 2 first character of the input voltage...

  • Page 9

    9 5. Installation. • read and respect any information as regards to safety, which is described in section 2 of this document. To ob- viate any of the described indications, can cause serious or very serious injuries to persons with direct contact or accidents in the vicinity, as well as failures in ...

  • Page 10

    10 salicru • the data in the nameplate of the equipment shows the nominal currents only as the safety standard en-iec 62040-1 states. The overload conditions are considered as a nonpermanent and exceptional operating mode. • if peripheral elements are going to be added at the input, output or bypass...

  • Page 11

    11 • when discrepancies between the labelling of the equipment and the instructions of this user’s manual exist, the labelling in the equipment will always prevail. • the references in bold between brackets, which are shown in the different points of this section, correspond to the ups elements iden...

  • Page 12

    12 salicru input line loads ouput ups input output aux. Cont. Output aux. Cont. Manual bypass ups input manual bypass ups output ups input ups output (*) aux. Cont. Manual bypass (1) output (2) manual bypass panel (*) aux. Cont. (1) available in manual bypass panel for ups's of adapt, cube3+ and x-t...

  • Page 13

    13 the ups auxiliary terminals are labelled as follows, de- pending on the product series: adapt, pins 1 and 2 of (jp5) . Cube3+, two terminal strip (x51) . X-tra, terminals (mby1) and (mby2) . • the way of connecting the control cables of the ups’s with the panel will differ depending on the ups se...

  • Page 14

    14 salicru input line loads ouput manual bypass aux. Cont. Ups 1 manual bypass (1) ••• ups «n» manual bypass (1) ups 1 output (2) ••• ups «n» output (2) ups 1 input input output aux. Cont. Output aux. Cont. Bypass manual manual bypass panel ups «n» ups «n » input ups 1 output ups «n » output ••• ups...

  • Page 15

    15 input line loads ouput input static bypass output aux. Cont. Output aux. Cont. Bypass manual manual bypass panel ups «n» ups 1 output ups «n » output ups 1 ups 1 input ups «n » input input static bypass output aux. Cont. Output aux. Cont. Bypass manual ••• ••• ••• manual bypass aux. Cont. Ups 1 m...

  • Page 16

    16 salicru 6. Start up and shutdown. • these instructions are generic for any manual bypass panel of this series, parallel and redundant equipments included. Omit those manoeuvring of the switches that your unit doesn’t have. • the references in bold between brackets, which are shown in the differen...

  • Page 17

    17 • start up the ups according to the procedure stated in the «user’s, installation and start up manual» of the equipment. The bypass panel supplies voltage to the terminals labelled as «loads output». Ups input static bypass manual bypass ups output on on off + on fig. 11. Position of the bypass p...

  • Page 18

    18 salicru 6.3.2. Manual bypass panel with two or more ups’s. • put all the ups’s on bypass (inverters «off») , according to the procedure stated in the «user’s, installation and start up manual» of the ups. It is essential to shutdown the inverters of the ups’s before proceeding, otherwise a short-...

  • Page 19

    19 6.4.2. Manual bypass panels with two or more ups’s. • once the preventive maintenance, fixing or ups or ups’s replacing tasks have been finished, loads must be shifted to them, but checking the following points previously: ups’s switches are turned «off». Bypass panel switches, less the «manual b...

  • Page 20

    Avda. De la serra 100 08460 palautordera barcelona tel. +34 93 848 24 00 fax +34 93 848 22 05 services@salicru.Com salicru.Com www.Linkedin.Com/company/salicru @salicru_sa product range uninterruptible power supplies (ups) lighting flow dimmer-stabilisers dc power systems static inverters photovolta...