Salicru SLC ADAPT User Manual - page 12
12
SALICRU
INPUT LINE
LOADS OUPUT
UPS
INPUT
OUTPUT
Aux. cont. output
Aux. cont. manual bypass
UPS INPUT
MANUAL
BYPASS
UPS OUTPUT
UPS INPUT
UPS OUTPUT
(*) Aux. cont.
Manual Bypass
(1)
Output
(2)
MANUAL BYPASS
PANEL
(*) Aux. cont.
(1)
Available in manual bypass panel for UPS's of ADAPT, CUBE3+ and X-TRA series.
(2)
Available in manual bypass panel for UPS's of CUBE3+ series only.
(1) and (2)
Not available in manual bypass panels for UPSs of TWIN PRO and PRO 33 series.
Fig. 3. Generic manual bypass panel for standard UPS.
INPUT LINE
STATIC
BYPASS
INPUT LINE
LOADS OUPUT
UPS OUTPUT
UPS INPUT
UPS STATIC
BYPASS
STATIC BYPASS
MANUAL
BYPASS
UPS OUTPUT
(*) Aux. cont.
Manual Bypass
(1)
Output
(2)
UPS INPUT
INPUT
STATIC BYPASS
OUTPUT
Aux. cont. output
Aux. cont. manual bypass
MANUAL BYPASS
PANEL
UPS
(*) Aux. cont.
(1)
Available in manual bypass panel for UPS's of ADAPT, CUBE3+ and X-TRA series.
(2)
Available in manual bypass panel for UPS's of CUBE3+ series only.
(1) and (2)
Not available in manual bypass panels for UPS's of TWIN PRO and PRO 33 series.
Fig. 4. Generic manual bypass panel for a UPS with
separate bypass line.
5.3.7. Systems with «n» equipments in parallel or
redundant.
5.3.7.1. Power connections.
•
Make the connections stated in sections 5.3.1 and 5.3.2.
•
Make and repeat for each equipment that makes the
system, the connections stated in section 5.3.3.
5.3.7.2. Connection of the auxiliary contact of the manual bypass
switch of each UPS, with the one in the bypass panel (not
available in panels of TWIN PRO and PRO 33 series).
•
By means of control wiring (minimum 1 mm
2
and
maximum 2,5 mm
2
), it is mandatory to connect the
terminal strip labelled as «BYPASS AUXILIARY CONTACT» of
the UPS with the ones in the bypass panel. These signal ter-
minals are the extension of the normally opened auxiliary
contact, of its respective internal manual bypass.