OPV
220
230
Fig. 20. LCD panel setting
To exit from setting mode, press once the “Enter” button; to continue
setting, press “Select” button. If no pressing is done over the “Se-
lect” or “Enter” button for more than 10 seconds, the setting mode
is automatically cancelled.
The output frequency string “OPF”, Bypass status string ” bYPA”,
operating mode string “MOdE”, External Battery Pack Number
string “EbPN”, remaining back up time string “bATT”, Charger cur-
rent string”CHG” would be presented cyclically. Only one voltage
figure can be selected “220V”, “230V”, “240V” at any time; only
one frequency figure can be selected “50Hz”, “60Hz” at any time;
Bypass status can be selected “000” or “001”(000 means Bypass
Disabled,001 means Bypass Enabled), if bypass is enabled the UPS
would shift to bypass mode in several seconds, or if bypass is disa-
bled the UPS would shift to no output mode; Operating mode can be
selected “UPS”, “ECO”or “CVF” (“UPS” means normal mode, “ECO”
means the high efficiency mode, and “CVF” means the fequency
converter mode), to set the operating mode is only available after
turning in the UPS; External Battery Pack Quantity can be selected
from “000” to “009” (“009” means 9 external battery pack); Charger
Current can be selected to 3.0/6.0 for 0,7kVA/1kVA “B1”equipments
and 1.5/3.0/4.5/6.0 for 1,5kVA/2kVA/3kVA “B1”equipments (3.0
means 3A charger); remaining back up time function can be selected
to “000” or “001” (000 means remaining back up time function disa-
bled, so the remaining back up time would not be displayed in the
LCD panel when the UPS is on battery mode, and 001 means re-
maining back up time function enabled, so the remaining back up
time is displayed (in Min or Sec) when the UPS is on battery mode
and the string “bATT” would be displayed in the LCD every 2s).
Next it is shown an example to set the Operating mode from normal
to frequency converter mode through the LCD panel.
OPV
220
230
Step 1:
“OPV” is displayed after pressing the “Enter” button.
OPF
220
500
.
Step 2:
“OPF” is displayed after pressing the “Select” button.
bYPA
220
000
Step 3:
“bYPA” is displayed after pressing the “Select” button.
MOdE
220
UPS
Step 4:
“MOdE” is displayed after pressing the “Select” button.
“UPS” is blinking after pressing the “Enter” button.
MOdE
220
ECO
Step 5:
“ECO” is blinking after pressing the “Select” button.