Samlexpower SEC-1250UL Owner's Manual - Section 6 |
16 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 17
seCtIOn 6 |
Installation
locAtion, MoUntinG And SAFety
Thechargerisrequiredtobeinstalledinasafe,wellventilatedanddrylocation.
Pleaseseethedetailsgivenunder“ImportantSafetyPrecautions”.Thechargercanbe
mountedhorizontallyorvertically.Whenmountingverticallyonawallorabulkhead,
pleaseensurethattheaxisofthefanrotorishorizontali.e.thefanexhaustopening
shouldfaceleftorrightbutNOTfaceupordown.
WARninG!
Mountingtheunitverticallyonaverticalsurfacewiththefanopeningfacing
upordownisNOTallowedforsafety.Thisistopreventfallingofobjectsinto
the unit through the fan grille when the fan opening faces up. If fan opening
facesdown,hotdamagedcomponentsmayfallout.
oUtPUt connectoRS
Connectorswithtubular,screwdowntypeofterminalsareusedforoutputconnection.
Thediameterofthetubularholeoftheconnectoris8mm(0.31inches).Twopositive
outputconnectors(1,2)areprovidedforconnectingtothePositiveterminalsofthe2
banksofbatteries.Onecommonconnector(3)isprovidedfortheNegative
connection.
teRMinAl lUGS FoR connection to tHe cHARGeR
Forfirmconnectionwhenusingstrandedwire,crimp/solder“pin”styleterminallugs
onthechargerendoftheDCwiresusedforconnectingtothebattery/otherDCloads.
3piecesof“pin”styleterminallugshavebeenprovidedasfollows:
• ForSEC-1250UL WillaccommodateuptoAWG#4wire
• ForSEC-2425UL WillaccommodateuptoAWG#8wire
WiReS
Toavoidpolarityerrorsandpossibledamage,neverusewiresofonlyonecolor.UseRed
insulatedwire(s)forPositiveconnection(s)andBlackforNegativeconnection(s).
RecommendedDCwiresizesaregivenbelow(Basedonavoltagedropof2%).The
lengthinfeetisthelengthofthepairofthepositiveandnegativeDCwiresfromthe
chargertothebattery/otherDCloads.
distance From Battery
Sec-1250Ul
Sec-2425Ul
Up to 6 ft.
AWG#6
AWG#10
6 to 10 ft
AWG#4
AWG#8
10 to 20 ft.
AWG#1/0
AWG#6
teRMinAtion oF WiRe endS
Forfirmconnectionwhenusingstrandedwire,wireendsfortheconnectiontothe
chargershouldbeterminatedwithpintypesoflugsthathavebeenprovided.