Between Indoor unit and Outdoor unit Connection Cable Specifications(Common in use)
Power supply
Communation Cable
Power supply
Max/Min(V)
Indoor Power Cable
1Φ, 208~230V, 60Hz
±10%
0.0039 in²
, 3wires
0.0011~0.0023 in², 2wires
f Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
When installing the indoor unit in a computer room or network room, use the
double shielded (Tape aluminum / polyester braid + copper ) cable of FROHH2R
type.
1-phase terminal block spec
AC power : M5 screw
Communication : M4 screw
1(L)
2(N)
N
L
0.59
0.47
0.40
0.45
L1 (L) L2 (N) L1 (L) L2 (N)
INDOOR
POWER
OUTDOOR
POWER