TA ACON 34 User Manual - 0-10 V to 24 V Converter
2.
0-10 V to 24 V converter
Some boiler manufacturers use a 0-24 V signal in their products, which this converter
supplies.
Accuracy +/- 0.5 V at an internal resistance of the boiler controller of > 3 k
3.
Freely adjustable level converter
The third input makes it possible to divide or amplify the input signal. The input signal can be
a 0-10 V voltage or 0-20 mA current (depending on jumper position); the output signal is
always a voltage.
3.1 Input signal
– 0-10 V voltage
The jumper must be in position "U".
3.1.1. Voltage amplification
The output supplies 1 to 5 times the value of the input signal.
The amplification factor is set at the right-hand potentiometer. The
potentiometer setting must be established by taking measurements with
a multimeter.
Please note that the output signal is limited to approx. 25 V even at higher amplification
levels.
0-24 V signal
Earth
0-10 V signal
Earth
0-10 V signal
Earth
Earth
Voltage amplification
Jumper position "U"