Trion HE Plus 1400 Installation & Operation Manual - page 6
High Altitude Operation
Because the air is less dense at higher altitudes, there
is a possibility of nuisance arcing in the Electronic Air
Cleaner. The homeowner can quickly and easily correct
this condition.
1.
Make sure the HVAC System Blower is not
operating, the ON/OFF switch is in OFF position
and the circuit breaker is turned OFF or input
power cord is disconnected.
2.
Remove the Front Panel Assembly.
3.
Remove the cover from the Power Tray Assembly
by removing the two screws on top of unit. (The
entire Power Tray Assembly may be removed from
the cabinet by removing two screws from inside the
cabinet.)
4.
Locate the jumper terminal.
5.
With a pair of needle nose pliers, carefully relocate
the jumper settings from HIGH to MED. Ensure
that the jumper is firmly seated in the terminal.
6.
Replace the Power Tray Cover and secure it with
two screws.
7.
Replace the Front Panel Assembly, turn circuit
breaker ON, reconnect input power cord and turn
ON/OFF switch ON.
This procedure will slightly reduce the output voltage,
minimize arcing and reduce ozone production. If the
condition does not improve, repeat the above
procedure and move the jumper setting from MED (M)
to LOW (L).
This unit is produced at the factory with the jumpers set
in the HIGH (H) position. However, the output voltage
may be lowered in any situation where the unit is arcing
excessively or there is excessive ozone.
Operation
4