Valdorf GT8600G Installation And Operation Manual - page 21
19
Gas Conversion and Specifications
- All Other Markets:
(*) NOTE:
Measure Burner operating pressure at manifold test point with both burners operating at
'High Flame' setting.
NAT, LPG & Butane Only - Operating pressure is ex-factory set and is not to be adjusted,
unless when converting between gasses, if required.
TOWN GAS Only -Adjust burner operating pressure using adjustable gas regulator
supplied.
Refer to the details in this section for further details.
Natural Gas
Town Gas
Main Burner Injectors
Ø 2.10mm
Ø 3.80mm
Pilot Burner Injectors
0.35 0.60
Low Fire Adjustment
1 turn out (ccw)
2 turns out (ccw)
Burner Operating Pressure (*)
1.0kPa (*)
0.63kPa (*)
Main Burner Aeration Shutter
Fully Open
Fully Open
Gas Regulator Cap Screw
Adjustable Regulator
(Adjust to Burner
Operating Pressure)
LP Gas (Propane)
Butane
Main Burner Injectors
Ø 1.30mm
Ø 1.20mm
Pilot Burner Injectors
0.23 0.23
Low Fire Adjustment
½ turn out (ccw)
½ turn out (ccw)
Burner Operating Pressure (*)
2.5kPa (*)
2.5kPa (*)
Main Burner Aeration Shutter
Fully Open
Fully Open
Gas Regulator Cap Screw