Vega VEGADIS 82 Operating Instructions Manual

Manual is about: External display and adjustment unit for 4-20 mA/HART sensors

Summary of VEGADIS 82

  • Page 1

    Operating instructions external display and adjustment unit for 4 … 20 ma/hart sensors vegadis 82 4 … 20 ma/hart document id: 45300

  • Page 2: Contents

    2 contents vegadis 82 • 4 … 20 ma/hart 45300-en-140506 contents 1 about this document 1.1 function ........................................................................................................................... 4 1.2 target group .............................................................

  • Page 3

    3 contents vegadis 82 • 4 … 20 ma/hart 45300-en-140506 8.2 asset management function ........................................................................................... 50 8.3 rectify faults ........................................................................................................

  • Page 4: 1  About This Document

    4 1 about this document vegadis 82 • 4 … 20 ma/hart 45300-en-140506 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tionsformaintenanceandfaultrectification.Pleasereadthisinfo...

  • Page 5: 2  For Your Safety

    5 2 for your safety vegadis 82 • 4 … 20 ma/hart 45300-en-140506 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the ...

  • Page 6

    6 2 for your safety vegadis 82 • 4 … 20 ma/hart 45300-en-140506 youcanfindtheconformitycertificateinthedownloadsectionunder www.Vega.Com. 2.6 namur recommendations namur is the automation technology user association in the process industry in germany. The published namur recommendations are accepted...

  • Page 7: 3  Product Description

    7 3 product description vegadis 82 • 4 … 20 ma/hart 45300-en-140506 3 product description 3.1 configuration the type label on the housing contains the most important data for identificationanduseoftheinstrument: 2 3 1 5 6 4 12 11 10 9 8 7 fig. 1: layout of the type label (example) 1 instrument type ...

  • Page 8

    8 3 product description vegadis 82 • 4 … 20 ma/hart 45300-en-140506 • hardware from 1.0.0 the scope of delivery encompasses: • display and adjustment unit • mounting accessories (optional) • documentation – this operating instructions manual – ex-specific"safety instructions" (with ex versions) – if...

  • Page 9

    9 3 product description vegadis 82 • 4 … 20 ma/hart 45300-en-140506 4 5 3 1 2 fig. 2: connection of the vegadis 82 to the sensor, adjustment via the display and adjustment module 1 voltage supply/signal output sensor 2 vegadis 82 3 display and adjustment module 4 4 … 20 ma/hart signal cable 5 sensor...

  • Page 10

    10 3 product description vegadis 82 • 4 … 20 ma/hart 45300-en-140506 adjustment range: sensor adjustment, indication scaling vegadis 82 hart multidrop: the vegadis 82 can be also used as an indicating device for a bus participant in a hart multidrop system. Adjustment range: sensor adjustment for a ...

  • Page 11

    11 3 product description vegadis 82 • 4 … 20 ma/hart 45300-en-140506 parameter adjustment of these instruments, the adjustment software pactware with vega-dtm is required. Youcanfindfurtherinformationintheoperatinginstructions"interface adapter vegaconnect" (document-id 32628). The electronics modul...

  • Page 12: 4 Mounting

    12 4 mounting vegadis 82 • 4 … 20 ma/hart 45300-en-140506 4 mounting 4.1 general instructions vegadis 82 functions in any installation position. Protect your instrument against moisture penetration through the fol- lowing measures: • use the recommended cable (see chapter "connecting to power supply...

  • Page 13

    13 4 mounting vegadis 82 • 4 … 20 ma/hart 45300-en-140506 1 2 fig. 5: vegadis 82 with plastic housing for carrier rail mounting 1 base 2 carrier rail the versions with aluminium or stainless steel housing for carrier rail mounting according to en 50022 are supplied with unassembled mounting accessor...

  • Page 14

    14 4 mounting vegadis 82 • 4 … 20 ma/hart 45300-en-140506 2 1 3 fig. 7: vegadis 82 for tube mounting 1 4 screws m5 x 100 2 mounting brackets 3 tube (diameter 1" to 2") the vegadis 82 is also available with a plastic housing for panel mounting. The housing is fastened to the rear of the panel by mean...

  • Page 15

    15 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-140506 5 connecting to power supply 5.1 preparing the connection always keep in mind the following safety instructions: • connect only in the complete absence of line voltage • if overvoltage surges are expected, overvoltage arrest...

  • Page 16

    16 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-140506 5.2 connection technology and steps the voltage supply and signal output are connected via the spring- loaded terminals in the housing. Connection to the display and adjustment module or to the interface adapter is carried o...

  • Page 17

    17 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-140506 8. Connect the screen to the internal ground terminal, connect the outer ground terminal to potential equalisation 9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable 10....

  • Page 18

    18 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-140506 5.5 connection hart multidrop thefollowingillustrationsshowinasimplifiedwaytheuseofve- gadis 82 in conjunction with several hart sensors. Note: if the instrument is powered via a vegamet signal conditioning instrument, then ...

  • Page 19

    19 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-140506 + - 1 2 3 4 18 17 16 15 1413 1211 10 9 8 7 6 5 n- l1+ + - on 1 2 1 2 % 1 2 3 fig. 13: connection of the vegadis 82 as external indication to signal condi- tioning instrument or four-wire sensor 1 sensor 2 signal conditioning...

  • Page 20

    20 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-140506 5.7 connection example 1 3 2 4 5 1 2 + ( ) (-) 6 7 8 4...20ma sensor 1 2 + ( ) (-) power supply 3 4 + ( ) (-) r off on hart fig. 15: connection example 4 … 20 ma/hart 1 voltage supply 2 vegadis 82 3 connection cable 4 sensor...

  • Page 21: Module

    21 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 6 set up with the display and adjustment module 6.1 short description the display and adjustment module is used for measured value display, adjustment and diagnosis. It can be mounted in the following hous...

  • Page 22

    22 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 fig. 16: installation of the display and adjustment module 6.3 adjustment system 1 2 fig. 17: display and adjustment elements 1 lc display 2 adjustment keys • [ok] key: – move to the menu overview – confir...

  • Page 23

    23 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 • [-] key: – presentation, change measured value – select list entry – select editing position • [+] key: – change value of the parameter • [esc] key: – interrupt input – jump to next higher menu the instr...

  • Page 24

    24 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 the selection branches into the following menus for parameter adjust- ment of the vegadis 82 or the connected sensor. Note: the symbol "s" is displayed in the upper right corner of the display if there is ...

  • Page 25

    25 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 the following languages are available: • german • english • french • spanish • russian • italian • dutch • portuguese • turkish • polish • czech inthismenuitemyoudefinetheindicationofthemeasuredvalues on t...

  • Page 26

    26 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 in the menu item "scaling variable"youdefinethescalingvariable and unit of the measured value on the display, e.G. Volume in l. Inadditiontotheofferedstandardunits,thereisthepossibility,tocre- ateauser-def...

  • Page 27

    27 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 the following reset functions are available: delivery status: restores the parameter settings at the time of ship- mentexfactoryincludingtheorder-specificsettings. Basic settings: resetting the parameter s...

  • Page 28

    28 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 with the parameter "hart master mode"youdefinetheinstrument function as either primary or secondary master. The parameter "hart address",definestheaddressofthesensor vegadis 82 communicates with via hart. ...

  • Page 29

    29 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 setup: settings, for example, for medium, application, vessel form, adjustment, signal output diagnosis: information, for example on the instrument status, peak value, reliability, echo curve memory as wel...

  • Page 30

    30 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 storage tank with product circulation: • setup: large-volumed, upright cylindrical, spherical • productspeed:slowfillingandemptying • vessel: small laterally mounted or large top mounted stirrer • process/...

  • Page 31

    31 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 • process/measurement conditions: – condensation, buildup on the antenna – foam generation • properties, sensor: – measurementspeedoptimizedbyvirtuallynoaveraging – sporadic false echoes are suppressed – f...

  • Page 32

    32 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 • properties, sensor: – false signals outside the vessel are not taken into consideration – false signal suppression recommended transportable plastic tank: • vessel: – materialandthicknessdifferent – meas...

  • Page 33

    33 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 – instrument demonstration – object recognition/monitoring (additional settings required) • properties, sensor: – sensor accepts all measured value changes within the measur- ing range immediately – high s...

  • Page 34

    34 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 2 3 1 0,5 m (19.68 ") 5 m (196.85 ") 100% 0% fig. 18: parameter adjustment example min./max. Adjustment 1 min. Level = max. Meas. Distance 2 max. Level = min. Meas. Distance 3 reference plane = starting po...

  • Page 35

    35 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 3. Set the requested percentage value with [+] and save with [ok]. The cursor jumps now to the distance value. 4. Enter the suitable distance value in m for the empty vessel (e.G. Distance from the sensor ...

  • Page 36

    36 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 the "false signal suppression" displays the saved false echoes (see menu "additional settings") of the empty vessel with signal strength in "db" over the measuring range. A comparison of echo curve and fal...

  • Page 37

    37 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 2. Confirmagainwith[ok]. 3. Confirmagainwith[ok]. 4. Confirmagainwith[ok] and enter the actual distance from the sensor to the product surface. 5. All interfering signals in this section are detected by th...

  • Page 38

    38 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 required. Corresponding linearisation curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. By activating the appropriate curve, the vol...

  • Page 39

    39 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 the following table shows the default values of the instrument. De- pending on the instrument version, not all menu items are available or differentlyassigned: menu menu item default value setup measuremen...

  • Page 40

    40 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 source data as well as the target sensor are displayed. If the data do not match, a failure message is outputted or the function is blocked. The data are only saved after release. In this menu item, you ca...

  • Page 41

    41 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 after the position correction is carried out, the actual measured value is corrected to 0. The corrective value appears with an inverse sign as offsetvalueinthedisplay. The position correction can be repea...

  • Page 42

    42 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 2. Edit the percentage value with [ok] and set the cursor to the requested position with [->]. 3. Set the requested percentage value (e.G. 10 %) with [+] and save with [ok]. The cursor jumps now to the pre...

  • Page 43

    43 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 centageandvesselvolume.Thelinearizationappliestothemeasured value indication and the current output. Caution: note the following, if the respective sensor is used as part of an over- fillprotectionsystemac...

  • Page 44

    44 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 menu item parameter default value adjustment min. Adjustment 0.00 bar 0.00 % max. Adjustment nominal measuring range in bar 100.00 % damping integration time 0 s reset - diagnosis menu item parameter defau...

  • Page 45

    45 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 in this menu item, the adjustment unit of the instrument is determined. The selection determines the displayed unit in the menu items "lower range" and "upper range". Unit of measurement: enter the request...

  • Page 46

    46 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-140506 4. Enter the pressure value corresponding to the min. Level (e.G. 0 mbar). 5. Save settings with [ok] and move with [esc] and [->] to the max. Adjustment. Theadjustmentofthelowerrangeishencefinished. Todam...

  • Page 47: Pactware

    47 7 setup instrument and sensor with pactware vegadis 82 • 4 … 20 ma/hart 45300-en-140506 7 setup instrument and sensor with pactware 7.1 connect the pc the pc is connected via the interface adapter to the vegadis 82. Parameter adjustment options: • vegadis 82 • sensor 3 1 2 fig. 20: connection of ...

  • Page 48

    48 7 setup instrument and sensor with pactware vegadis 82 • 4 … 20 ma/hart 45300-en-140506 1 3 6 5 2 4 sensor 1 2 + ( ) (-) power supply 3 4 + ( ) (-) r off on hart fig. 21: connecting the pc via hart to the signal cable 1 processing system/plc/voltage supply 2 vegadis 82 3 to the sensor 4 connectio...

  • Page 49

    49 7 setup instrument and sensor with pactware vegadis 82 • 4 … 20 ma/hart 45300-en-140506 fig. 22: example of a dtm view all device dtms are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are alr...

  • Page 50: 8  Diagnostics and Service

    50 8 diagnostics and service vegadis 82 • 4 … 20 ma/hart 45300-en-140506 8 diagnostics and service 8.1 maintenance if the device is used correctly, no maintenance is required in normal operation. 8.2 asset management function the instrument supports the self-monitoring and diagnosis of the con- nect...

  • Page 51

    51 8 diagnostics and service vegadis 82 • 4 … 20 ma/hart 45300-en-140506 code text mes- sage cause rectification e034 eeprom: crc error – eeprom: crc error – switchtheinstrumentoff and on – carry out reset to default setting – send instrument for repair e035 rom: crc error – rom: crc error – switcht...

  • Page 52

    52 8 diagnostics and service vegadis 82 • 4 … 20 ma/hart 45300-en-140506 error cause rectification 4 … 20 ma signal missing – electrical con- nection faulty – check connection according to chapter "connection steps" and if necessary, correct according to chapter "wiring plan" – voltage supply missin...

  • Page 53

    53 8 diagnostics and service vegadis 82 • 4 … 20 ma/hart 45300-en-140506 caution: instruments with approvals can be bound to certain software versions. Thereforemakesurethattheapprovalisstilleffectiveafterasoftware update is carried out. Youcanfinddetailedinformationatwww.Vega.Com/downloads and "app...

  • Page 54: 9 Dismounting

    54 9 dismounting vegadis 82 • 4 … 20 ma/hart 45300-en-140506 9 dismounting 9.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Take note of chapters "mountin...

  • Page 55: 10 Supplement

    55 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-140506 10 supplement 10.1 technical data materials and weights materials Ʋ plastic housing plastic pbt (polyester) Ʋ aluminium housing aluminium die-casting alsi10mg, powder-coated - basis: polyester Ʋ stainless steel housing 316l precision casti...

  • Page 56

    56 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-140506 signal and supply circuit voltage drop with current value 4 … 20 ma Ʋ without lighting max. 1.7 v Ʋ with lighting max. 3.2 v Ʋ with activated hart resistance ad- ditionally max. 4.5 v hart resistance 200Ω current range 3.5 … 22.5 ma 1) ove...

  • Page 57

    57 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-140506 process conditions vibration resistance 4gat5…200hzaccordingtoen60068-2-6(vibration with resonance) vibration resistance with carrier rail mounting 1gat5…200hzaccordingtoen60068-2-6(vibration with resonance) shock resistance 100 g, 6 ms ac...

  • Page 58

    58 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-140506 10.2 hart communication the hart protocol operates with frequency shift keying (fsk) based on the data communication standardbell202.Thedigitalsignalisgeneratedfromthefrequencies1200and2200hz,which represent the bit information 1 and 0. Si...

  • Page 59

    59 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-140506 vegadis 82 - plastic housing - panel mounting 72,5 mm (2.85") 72,5 mm (2.85" ) 78,2 mm (3.08" ) 22,5 mm (0.89") 70 mm (2.76") 77 mm (3.03" ) 67 mm (2.64" ) 56 mm (2.20") 76 mm (2.99") fig. 24: vegadis 82 with plastic housing for panel moun...

  • Page 60

    60 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-140506 vegadis 82 - stainless steel, precision cast housing ø 86 mm (3.39") ~ 75 mm (2.95") 87 mm (3.43" ) 82 mm (3.23" ) 97 mm (3.82" ) 5 mm (0.2") 97 mm (3.82") fig. 26: vegadis 82 with stainless steel, precision cast housing mounting elements ...

  • Page 61

    61 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-140506 ø 29...60 mm (1.14"...2.36") 82 mm (3.23" ) 15 mm (0.59" ) 97 mm (3.82" ) 20 mm (0.79") m6 2 mm (0.08" ) 20 mm (0.79" ) 2 mm (0.08" ) 20 mm (0.79") 48...84 mm (1.89"...3.31") fig. 28: brackets for tube mounting of vegadis 82.

  • Page 62

    62 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-140506 10.4 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Only in u.S.A.: further information see patent label at the sensor housing. Vega produktfamilien s...

  • Page 63: Index

    63 index vegadis 82 • 4 … 20 ma/hart 45300-en-140506 index a adjustment 34, 35, 41 – lower range 45 – max. Adjustment 42 – menu 24, 40, 44 – min. Adjustment 41 – system 23 – unit 45 – upper range 45 adjust the indication 25 area of application 8 c change the language 24 check output signal 51 connec...

  • Page 64

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 45300-en-140506 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...