Vega VEGAPULS 64 Quick setup manual
Summary of VEGAPULS 64
Page 1
Quick setup guide radar sensor for continuous level measurement of liquids vegapuls 64 4 … 20 ma/hart - two-wire document id: 51462.
Page 2: Contents
2 contents vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 contents 1 for your safety 1.1 authorised personnel ....................................................................................................... 3 1.2 appropriate use ..........................................................
Page 3: 1 For Your Safety
3 1 for your safety vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 1 for your safety 1.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the...
Page 4
4 1 for your safety vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 1.5 ce conformity thedevicefulfillsthelegalrequirementsoftheapplicableecguide- lines.Byaffixingthecemarking,weconfirmsuccessfultestingofthe product. Youcanfindthececertificateofconformityinthedownloadsection of our homepage....
Page 5
5 1 for your safety vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 pleasehelpusfulfillthisobligationbyobservingtheenvironmental instructions in this manual: • chapter "packaging, transport and storage" • chapter "disposal".
Page 6: 2 Product Description
6 2 product description vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 2 product description 2.1 configuration thetypelabelcontainsthemostimportantdataforidentificationand use of the instrument: 2 1 12 11 10 9 5 6 4 3 7 8 fig. 1: layout of the type label (example) 1 instrument type 2 produc...
Page 7: 3 Mounting
7 3 mounting vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 3 mounting 3.1 mounting preparations, mounting strap the mounting strap is supplied unassembled (optionally) and must be screwed to the sensor before setup with three hexagon socket screws m5 x 10 and spring washers. Max. Torque, s...
Page 8
8 3 mounting vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 information: whenthehousingisrotated,thedirectionofpolarizationchanges andhencetheinfluenceofthefalseechoonthemeasuredvalue. Please keep this in mind when mounting or making changes later. When mounting the sensor, keep a distance ...
Page 9
9 4 connecting to power supply vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 4 connecting to power supply 4.1 connecting the voltage supply and signal output are connected via the spring- loaded terminals in the housing. Connection to the display and adjustment module or to the interface a...
Page 10
10 4 connecting to power supply vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 fig. 7: connection steps 5 and 6 - double chamber housing 6. Insert the wire ends into the terminals according to the wiring plan information: solidcoresaswellasflexiblecoreswithwireendsleevesareinsert- eddirectl...
Page 11
11 4 connecting to power supply vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 5 1 2 + ( ) (-) 6 7 8 4...20ma 2 3 4 1 fig. 8: electronics and terminal compartment, single chamber housing 1 voltage supply, signal output 2 for display and adjustment module or interface adapter 3 for external ...
Page 12: Module
12 5 set up with the display and adjustment module vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 5 set up with the display and adjustment module 5.1 insert display and adjustment module the display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchoosea...
Page 13
13 5 set up with the display and adjustment module vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 1 2 fig. 10: installing the display and adjustment module in the double chamber housing 1 in the electronics compartment 2 in the terminal compartment note: ifyouintendtoretrofittheinstrumentwi...
Page 14
14 5 set up with the display and adjustment module vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 3. Application in this menu item you determine the application. 4. Vessel form in this menu item you specify the for of the vessel bottom and top. 5. Vessel height/measuring range in this menu ...
Page 15
15 5 set up with the display and adjustment module vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 the return to the measured value indication is carried out through the [->] or [esc] keys or automatically after 3 s the menu "extended adjustment" is available for further settings. Im- portan...
Page 16
16 5 set up with the display and adjustment module vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 100% 0% 0,5 m (19.68 ") 5 m (196.9 ") 2 1 3 fig. 11: parameter adjustment example min./max. Adjustment 1 min. Level = max. Measuring distance 2 max. Level = min. Measuring distance 3 reference ...
Page 17
17 5 set up with the display and adjustment module vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 menu - setup menu item parameter default setting measurement loop name sensor units distance in m temperature in °c application medium water based application storage tank vessel top/vessel bot...
Page 18
18 5 set up with the display and adjustment module vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 menu item parameter default setting peak values, ad- ditional temperature - curve indication echo curve - false signal sup- pression - simulation percent echo curve memory percent menu - additi...
Page 19
19 5 set up with the display and adjustment module vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 thefollowingcircumstancescauseinterferingreflectionsandcan influencethemeasurement: • high sockets • vessel installations such as struts • agitators • buildup or welded joints on vessel walls n...
Page 20
20 5 set up with the display and adjustment module vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 delete: an already created false signal suppression will be com- pletely deleted. This is useful if the saved false signal suppression no longer matches the metrological conditions in the vesse...
Page 21: 6 Supplement
21 6 supplement vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111 6 supplement 6.1 technical data electromechanical data - version ip 66/ip 67 and ip 66/ip 68; 0.2 bar options of the cable entry Ʋ cable entry m20 x 1.5, ½ npt Ʋ cable gland m20 x 1,5; ½ npt (cable ø see below table) Ʋ blind plu...
Page 22
22 notes vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111.
Page 23
23 notes vegapuls 64 • 4 … 20 ma/hart - two-wire 51462-en-160111.
Page 24
Printing date: 51462-en-1601 11 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subject to change without prior notice © vega grieshaber kg, schil...