TEMPERATURE SETBACK DELAY - HEAT
00-120
(20*) Select the time delay (in minutes) before the thermostat
will initiate the temperature setback and allow the room
temperature to drop to the setback temperature after the
room becomes unoccupied.
This feature prevents initiating temperature setback
prematurely while the guest is still in the room but in an area
where occupancy cannot be detected by the occupancy sensor.
Setting the “Temperature Setback Delay - Heat” to “00”,
disables the setback in the heat mode. Set to “00” to disable
EMS.
Thermostat Settings
MINIMUM SETBACK TEMPERATURE
52-72
(64°F) Select the “Minimum Setback Temperature” in °F.
Setback temperature is calculated by measuring PTAC unit’s
ability to attain “Recovery Temperature - Heat” within
“Temperature Recovery Time”.
If recovery is disabled (“Temperature Recovery Time” is set to
“0”) or if setback temperatures have not yet been calculated,
the “Minimum Setback Temperature” value will be used as the
setback temperature for heating.
If calculated setback temperature for heating is lower than
“Minimum Setback Temperature”, then the “Minimum Setback
Temperature” will be used as setback temperature for heating.
This feature allows defining the minimum temperature in a
room when room is unoccupied and the thermostat is in the
setback mode.
Thermostat Settings