14 Technical data
44
14.4
Extension cable
Only use permitted extension cables, see chapter Safety.
Refer to the following table for the required cross-section area of the exten-
sion cable:
Note:
Refer to the nameplate or the chapter Technical data (via the item
number) for the type designation and voltage rating of your machine.
US-Machines
WARNING
Electrical voltage.
Injuries from electrocution.
f Check power cable and extension cable for signs of damage.
f Only use extension cables for which grounded conductors are connected to
the plug and the coupling (only for machines of class rating I, see chapter
Technical Data).
Machines
Voltage
[V]
Extension
[m]
Cross-section
area of cable
[mm
2
]
EH 25/230
230 1~
< 20
1.5
< 33
2.5
< 52
4
< 77
6
Machines
Voltage
[V]
Extension
[m]
Cross-section
area of cable
[mm
2
]
EH 65/120
120 1~
< 21
1,5
< 35
2,5
< 55
4
< 82
6