If the wattage is not given for a particular tool or appliance, it can be
calculated by multiplying its voltage and amperage requirements:
Single Phase: VOLTS x AMPS = WATTS
Three Phase: VOLTS x AMPS x 1.732 x 0.8 = WATTS
4.3
Installation
Place the generator in an area where it will not be exposed to rain,
snow, or direct sunlight. Make sure it is positioned on firm, level
ground, so it will not slide or shift. Position the engine exhaust away
from areas where people may be present.
The surrounding area must be free from water and moisture. All
components must be protected from excessive moisture.