arameter Tables
6.1 Basic Settings
Menu
Selection
Description of Selection
Sensor Type
Color acc.to EN 60584
Temperature Range
PT100 sensor display with 1 decimal (e.g.
24.5)
no standardization
-
199.9 … +600°C,
depending on the
model
PT100 sensor displaying total degrees (e.g.
24)
no standardization
Cu50 sensor display with 1 decimal
no standardization
-
50 … +150°C
Thermo element type T Cu-CuNi
brown (+) / white (-)
-
200 … +400°C
Thermo element type R PtRh13-Pt
orange (+) / white (-)
-
50 … +1600°C
Thermo element type J Fe-CuNi
black (+) / white (-)
-
200 … +1200°C
Thermo element type Wre3-Wre25
no standardization
0 … +2300°C
Thermo element type B PtRh30-Pt
no standardization
+350 … 1800°C
Thermo element type S PtRh10-Pt
orange (+) / white (-)
-
50 … +1600°C
Thermo element type K Ni-CrNi
green (+) / white (-)
-
200 … +1300°C
Thermo element type E NiCr-CuNi
purple (+) / white (-)
-
200 … +900°C
0
Output relays J1 and J2 as ON/OFF function programmable without P.I.D. Outlet SSR relay
disabled. Suitable for two-point or differentiating temperature circuit
.
1
Output relay J1 as alarm and J2 as P.I.D. outlet without voltage pulse function (only on-off cycled),
2
Outlet relay programmable as in Mode 0; additionally activated SSR-P.I.D. outlet at clamps 6 (+)
and 7 (-) (voltage-impulse outlet approx. 10V=)
3
SSR outlet as ON/OFF operation (menu Hy = activated; P.I.D. deactivated).
4
J1 as alarm outlet; J2 as ON/OFF operation with running hysteresis value (Menu Hy); SSR outlet
disabled
; AH2 and AL2 inactive (table: Relays Outlets page 4)..
0 ...999°
Hysteresis value (restart delay) for SSR outlet for selection OUTY= 3
-100° ...+100°
Calibrating function for adjusting sensor deviations. Value will be added to the set value.
0
Operating mode “heating operation”. Controller will turn off load after rising temperature has
reached the set value (above set value = load cut off).
1
Operating ,mode “cooling operation”. Controller will turn off load when falling temperature has
reached the set value (below set value = load cut off)
0
Selection of unit for measuring and display = degrees Celsius
1
Selection of unit for measuring and display = degrees Fahrenheit
After selecting
, confirm your menu setting by pushing
SET
You will now automatically return to the menu selection or to the control mode.
Push the "SET" button and enter code 0089 in order to set the following parameters.
Use this table for the basic settings of the controller after connecting the control voltage
and the temperature sensor. The load can be connected, but does not have to.