INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12
997-012330-3-R
Installer Settings
NOTE: These options are intended to be used by the installer.
End users are not advised to change or modify any of these
settings. Doing so may make your equipment stop working
properly and/or may void the warranty of the thermostat as well
as the equipment connected to the thermostat. To access the
installer setting menu, press and hold the upper left corner of the
screen for at least 5 seconds to enter the installer screen.
Equipment
The system will auto detect the type of equipment connected an
displays it on this screen.
SINGLE STAGE/MULTI STAGE
Single Stage – Used with heat pumps with PSC motors
Multi Stage – Used with heat pumps with ECM motors,
either Single Speed or Dual Capacity
Variable Speed – Used with heat pumps with variable
speed compressors
Thermostat Type
NORMAL/DUAL FUEL
Normal – used for normal operation
Dual Fuel – used on dual fuel systems; needs outdoor
sensor to lockout dual fuel
Restore Defaults
This will allow you to revert to the factory default settings.
Humidity Settings
If your system is setup with a humidifier, or you desire a
dehumidification option, select the appropriate setting.
HUMIDIFY
DEHUMIDIFY
BOTH (H or DH)
NONE
NOTE: If you have an outdoor sensor attached to the
thermostat, the Humidification setting is adjusted automatically
based on the outdoor temperature.
Humidify - Turns on the H output when the room humidity is
below the set point and MODE is set to HEAT, EHEAT,
or AUTO when Heating was the last mode run.
Dehumidify – Turns on the DH output when the room
humidity is above the set point and the MODE is set to
COOL or AUTO when Cool was the last mode run.
Both – HUMIDIFY operates in the HEAT mode and
DEHUMIDIFY operates in COOL mode.
NONE – Neither is active.
Installer Setting Page Two
Press NEXT button. It will bring you to the second page of
installer setting.
Cycles Per Hour
This feature will not allow more than the specified number of
equipment cycles per hour. Values can range from 4 or 6 (or 1
cycle every 15 minutes (default) or 1 cycle every 10 minutes, if
6 is set). Factory default setting is 4. This default selection will
provide optimum performance in nearly all installations.