INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12
997-012330-3-R
Differential
This adjustment will vary the number of degrees, from the set
point, before a call for heating or cooling is made. Adjustments
can range between 0.5˚ and 4˚ differential. Default is 0.5˚ offset.
(If your set point is 70˚F in heating, your thermostat will not call
for heat until the temperature is 69.5˚F, with a 0.5 differential).
Smart Heat Staging (Heat Pump Only)
This delays 3rd stage heating for a set time. Options are ON
or OFF. Default is OFF. Range for this are 0-120 minutes in 5
minute increments. If set to ON, 30 minutes is the default time.
( If ‘ON’ is selected and the demand has not been satisfied the
thermostat will energize electric heat after the selected time has
expired regardless of demand.)
Smart Recovery
Smart recovery is a feature of your thermostat designed to
improve comfort by adjusting temperatures to achieve a room
temperature by the programmed time. When it’s time for a
programmed temperature change, smart recovery begins
working in advance, turning the system on and off as needed to
adjust the indoor temperature. During these transition periods,
you may notice that the actual temperature and your temperature
setting don’t match. That’s smart recovery in action, adjusting
temperatures in small increments for greater energy efficiency.
This is more energy efficient than simply allowing the system to
operate at full capacity until the desired temperature has been
met. Smart Recovery helps avoid excessive use of auxiliary heat
when recovering from night setback in the heating mode.
Electric Heat (Aux) Lockout
When an outdoor temperature sensor is installed, you can set it
up so the electric heat or Dual Fuel option doesn’t energize if the
outdoor temperature is above a certain temperature. Ranges for
this are NONE (default), 5˚F to 60˚F in 5˚ increments.
Cooling Lockout
When an outdoor temperature sensor is installed, it can be set
up so cooling option doesn’t energize if the outdoor temperature
is below a certain temperature. Ranges for this are NONE
(default), 45˚F, 50˚F, or 55˚F.
Remote Sensor
Allows selection of the remote sensor to determine indoor
temperature. Options are REMOTE SENSOR, AVERAGE, and
STAND ALONE. The REMOTE SENSOR is connected to the S1
and S2 on the thermostat terminals.
Compressor Satisfy
Normal – allows compressor downstaging from Y2 to Y1.
Recommended setting for most products.
Y2 Finish – Once the heat pump has engaged Y2 the
thermostat will not allow downstaging to Y1. The call is
satisfied in Y2.
Installer Setting Page Three
Press NEXT button. It will bring you to the installer setting page three.
Set Anticipator
This adjustment controls the sensitivity and cycle rate of the
thermostat. Higher numbers decrease the cycle rate. Lower
numbers increase the cycle rate. Default value is 0, and the
range is 0-4.
Accessories
Each of these options has settings for Cumulative Run Time
and Calendar Time. Messages will flash at the top of the Main
screen when these events are met to alert the owner that it is
time service these options.