Water Furnace TPCC32U01 Instruction Manual - page 7
7
INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12
997-012330-3-R
Air Filter - Cumulative Run Time default is 1000 hours and
Calendar Time is 6 months. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-48 months (in 3 month increments).
Humidifier - Cumulative Run Time default is 0 hours (OFF)
and Calendar Time is OFF. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-24 months (in 3 month increments).
UV Lamp - Cumulative Run Time default is 0 hours (OFF)
and Calendar Time is OFF. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-48 months (in 3 month increments).
Air Cleaner - Cumulative Run Time default is 0 hours (OFF)
and Calendar Time is OFF. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-24 months (in 3 month increments).
To cancel the message, select the CANCEL.
Offsets
Temperature Offsets – This option allows calibration (or
deliberate miscalibration) of the room temperature
sensor(s). There are various reasons why the
displayed temperature would be adjusted to a higher
or lower value. NOTE: Do not adjust for 30 minutes
after installation because board may be heated by
handling. The selected number is the number of
degrees, plus or minus, which will be added to actual
temperature. The numbers can range between -5˚ and
+5˚. Default values are set to 0˚ offset.
Temperature Offset
Remote Indoor Offset (if sensor is attached)
Outdoor Offset (if sensor is attached)
Humidity Offset – This option allows calibration of the
humidity sensor. Adjustments can range between -10%
and +10%. Default is 0% offset.
Auto Changeover
With auto changeover, the thermostat automatically switches
itself from heating to cooling, or vise versa, based on the
setpoints. When setting up the thermostat you have to enter
both a cooling setpoint and a heating setpoint. The thermostat
will also prevent the user from setting the cooling setpoint lower
than the heating setpoint. Mode is set to AUTO for this operation
to work.
Auto Changeover Time – This setting sets the minimum off
time before the thermostat can change from one mode
to another. Default is 5 minutes. Range is from 0-120
minutes in 15 minute increments.
Auto or Manual Change – Default is AUTO. If MANUAL
is chosen, you will need to change from heating to
cooling or vise versa. When MANUAL is set, AUTO is
removed from the MODE screen as a choice.
USB
Allows Import and Export of Installer Settings, User Settings,
Program, and Dealer Details.