WaterFurnace IntelliZone2 Installation Manual - Intellizone2
18
INTELLIZONE2
● 24V INSTALLATION MANUAL
IntelliZone2
● 24V Confi guration cont.
Thermostat Type
NORMAL/DUAL FUEL
Normal - Used for normal operation
Dual Fuel - Not Applicable - Operation is
not available with IntelliZone2
● 24V since it is a
non communicating system
Fan with Heat Option - Not Applicable
Aux Heat Lockout - Allows the configuration to lockout
electric heat above a selected outdoor temperature.
The outdoor sensor (OAT) must be installed on the
IntelliZone2 Relay Board. This setting is adjustable in 5°F
increments from NONE to 40°F. This will provide full heat
pump capacity without electric heat above the selected
temperature. When the outdoor temperature drops
below the selected temperature, then electric heat will be
energized when the demand is present.
Differential- This adjustment will vary the number of
degrees, from the set point, before a call for heating or
cooling is made. Adjustments can range between 0.2° and
4° differential. Default is 0.5° differential. (If your set point
is 70° in heating, your thermostat will not call for heat until
the temperature is 69.5°, with a 0.5° differential setting).
Offsets
Temperature Offsets – This option allows calibration
(or deliberate miscalibration) of the room
temperature sensor. The Offset function only
works on the MasterStat. There are various
reasons why the displayed temperature would be
adjusted to a higher or lower value. NOTE: Do not
adjust for 30 minutes after installation because
board may be heated by handling. The selected
number is the number of degrees, plus or minus,
which will be added to actual temperature. The
numbers can range between -5˚ and +5˚. Default
values are set to 0˚ offset.
Temperature Offset
Remote Indoor Offset (if sensor is attached)
Outdoor Offset (if sensor is attached)
Humidity Offset – This option allows calibration of the
humidity sensor. Adjustments can range between
-10% and +10%. Default is 0% offset.
Humidity - Not Applicable
Temperature Sensors - Allows the configuration of the
remote sensor to be remote only, average of remote and
internal, or no remote sensor. Allows the configuration of
the outdoor sensor to be zone panel, MasterStat, or no
outdoor sensor. Because IntelliZone2
● 24V ships standard
with an outdoor sensor this option needs to be selected.
NOTE: LAS on IntelliZone2 relay board = OAT
Accessories - Each of these options has settings for
Cumulative Run Time and Calendar Time. Messages will
flash at the top of the Main screen when these events are
met to alert the owner that it is time service these options.
Air Filter - Cumulative Run Time default is 1000 hours
and Calendar Time is 3 months. Values can range
from NONE-2500 hours for Cumulative Run Time
(in 100 hour increments), or Calendar Time can be
set to NONE to 12 months (in 3 month increments).
Humidifier - Cumulative Run Time default is NONE
hours (OFF) and Calendar Time is NONE Values
can range from NONE, 400-2500 hours for
Cumulative Run Time (in 100 hour increments), or
Calendar Time can be set to NONE, to 12 months
(in 3 month increments).