TROUBLESHOOTING
For any unexpected operation
1. Check DIP switch settings.
2. Make sure the switches are set according to the defined settings in the
DIP Switch Setting chart.
Lights do not turn ON with occupancy, and the following condition exists:
Red LED does not flash:
1. When power is initially applied to the sensor, there is a warm-up period
of up to 30 seconds before the red LED is active.
2. Check that the circuit breaker has been turned back on.
3. Check all sensor wire connections.
4. Make sure that PIR Sensitivity is set to 100% (DIP switch #5 set to OFF).
5. If it still does not flash, call 800.879.8585 for Technical Support.
LED flashes:
1. Check all sensor wire connections.
Lights do not turn OFF automatically:
1. The sensor technology (PIR) may be experiencing activations from
outside the controlled area or from some type of interference (see
“Unwanted Sensor Activations” below).
2. Check all sensor wire connections.
• Turn sensitivity and time delay to minimum and allow the sensor to
time out.
• If the lights turn off, the sensor is working properly (see number 1,
above, and “Sensor Adjustment” for readustment of sensor).
CAUTION
TURN POWER OFF AT THE CIRCUIT BREAKER
BEFORE WORKING WITH OR NEAR HIGH VOLTAGE.
Call 800.879.8585 for Technical Support