Wattstopper DW 100 Installation Instructions Manual - page 3
3
COVERAGE PATTERNS
Coverage testing has been performed according to the NEMA WD 7 guideline. For best performance, use in spaces not larger than
18' x 15'.
PIR Sensor
The sensor has a two-tiered, multi-cell viewing Fresnel lens with 180 degree field of
view. The red LED on the sensor flashes when the PIR detects motion.
Masking the Lens
Opaque adhesive tape is supplied so that sections of the PIR sensor’s view can be
masked. You can eliminate coverage in unwanted areas. Since masking removes
bands of coverage, take this into account when troubleshooting coverage problems.
Ultrasonic Sensor
The sensor has two ultrasonic transceivers operating at 40kHz. Detection sensitivity
can be adjusted using the trimpot under the ON/OFF buttons.
PIR
Coverage
7.5’
(2.2m)
15’
(4.5m)
20’
(6.1m)
35’
(10.6m)
Major motion
Minor motion
Ultrasonic
Coverage
10'
(3.0m)
7.5’
(2.2m)
20’
(6.1m)
15’
(4.5m)
Major motion
Minor motion
Top View
4’
(1.2m)
20’
(6.1m)
35’
(10.6m)
0
Side View
INSTALLATION
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
1. Make sure that the power has been turned
OFF at the circuit breaker.
2. Connect wires to the DW flying leads as shown in the wiring diagram below that is appropriate to the DW
model and electrical supply.
3. Attach the DW to the wall box by inserting screws into the two wide holes on the top and bottom of the
attached metal bracket. Match them up with the holes in the wall box and tighten.
4. Turn the circuit breaker
ON. Wait one minute, then push the ON/OFF button for each load and the lights
will turn
ON.
5. Test and adjust the sensor if necessary.
6. Attach the cover plate.
#12 – #14 AWG
Cu Wire Only
Strip Gage
1/2"
12.7mm
/RDG
5HG
/LQH%ODFN
1HXWUDO
*URXQG
*UHHQ
1HXWUDO:KLWH
DW-100 and DW-100-347 Wiring
Neutral
Ground
Blue
Line
Black
Secondary
Load
Brown
Primary
Load
Red
White
Neutral
White
Green
DW-200 Bi-Level Wiring
Blue
Ground
Primary
Load
Secondary
Load
Neutral
White
Red
Brown
Line 2
Line 1
Black
Neutral
White
Neutral
White
Green
DW-200 Dual Circuit Wiring