Pitch the horizontal run of the flue pipe upward 1/4 inch
(6.35mm) per foot (.305m) or more. Run directly to the
chimney, fasten joints securely and support horizontal
runs to prevent sagging.
If the flue pipe must be extra long, it’s size should be
increased. The horizontal length of the flue pipe should
not exceed the height of the chimney above the flue
connection.
The draft control should be hood type per Figure 2 or, IF
APPROVED BY LOCAL AUTHORITIES, a single
barometric damper suitable for gas firing per Figure 3.
The draft control should be sized the same as the flue
pipe per Figure 1, and should be located higher than the
highest part on the appliance flue passage. Refer to the
barometric draft regulator manufacturer’s instructions for
complete detail.
NOTICE: Should the flue pass through a partition,
the draft control must be located in the
same room as the heating appliance.
PITCH HORIZONTAL
RUN 1/4” (6.35mm) MIN.
PER FOOT (.305M)
VERTICAL
DRAFT HOOD
REDUCER
HORIZONTAL
DRAFT HOOD
CORROSION
RESISTANT LINING
DO NOT EXTEND
FLUE PIPE BEYOND
INSIDE OF CHIMNEY
PITCH HORIZONTAL
RUN 1/4” (6.35mm) MIN.
PER FOOT (.305M)
DRAFT HOOD POSITONS
Figure 2
BAROMETRIC DRAFT
CONTROL POSITION
Figure 3
TO PROTECT PROPERLY
LOCATE END OF BURNER
TUBE. POSITION TUBE 1/2”
(12.7mm) SHORT OF INSIDE
OF COMBUSTION
CHAMBER
EXISTING OR
ADDED TARGET
TO BACK OF COMBUS-
TION CHAMBER
HOT WATER OR STEAM BOILER WITH
COMBUSTION CHAMBER TARGET
Figure 5
TO PROTECT PROPERLY
LOCATE END OF BURNER
TUBE. POSITION TUBE 1/2”
(12.7mm) SHORT OF INSIDE
OF COMBUSTION
CHAMBER
CLEANOUT
SELECT EITHER
HORIZTONAL OR
VERTICAL DRAFT HOOD
EXISTING
PREFABRICATED
COMBUSTION
CHAMBER LINER
HOT WATER OR STEAM BOILER WITH
COMBUSTION CHAMBER LINER
Figure 6
TO PROTECT PROPERLY
LOCATE END OF BURNER
TUBE. POSITION TUBE 1/2”
(12.7mm) SHORT OF INSIDE
OF COMBUSTION
CHAMBER
CLEANOUT
CHIMNEY
FORCED AIR FURNACE
Figure 4
PAGE 3
SINGLE ACTING
BAROMETRIC
DRAFT CONTROL