Initial Operation
After the heater has been installed, the fuel supply system
is to be bled thoroughly.
NOTE:
Owing to the low fuel consumption it is required that the
heater be turned on repeatedly to fill the fuel line leading to
the heater.
During a test run of the heater all connections are to be
checked for leakage and security. Should a malfunction of
the heater occur during operation, fault isolating measures
are to be performed.
Shut-Down on Faults
Faults related to individual heater components and mal-
functions during the start-up sequence are detected in the
control unit.
The heater is shut down (fault lock-out) in the following
cases:
- unacceptable flame detector resistance
- insufficient temperature sensor resistance
- pencil-type glow plug/glow plug control defective
- insufficient fan speed, short circuit or interruption
- fault in the metering pump circuit or overheat protection
circuit (during start-up phase only)
- undervoltage of less than 10 volts or overvoltage of
more than 15 volts and for longer than 20 seconds
(aplies to 12-volt heaters)
- undervoltage of less than 20 volts or overvoltage of
more than 30 volts and for longer than 20 seconds
(on 24-volt heaters)
- control unit defective
No fuel is delivered in case of overheating.
An after-run cycle is performed as is the case when the
heater is shut down manually.
After the after-run cycle has been terminated, the control
unit is in the fault lock-out state.
An overheating condition is indicated by a flashing oper-
ation indicator.
Eliminate cause of malfunction.
To deactivate the fault lock-out, the heater is to be briefly
(min. 2 seconds) turned off and then switched back on
again
one time
.
Fault Code Display
If the heater is equipped with a combination or standard
digital timer, a fault code is indicated on the display of the
digital timer whenever a malfunction has occurred:
F 01 No start-up (after 2 start-up attempts)
F 02 Flame extinguished (repeated >5)
F 03 Undervoltage or overvoltage
F 04 Premature
flame
detection
F 05 Flame detector interruption or
flame detector short-circuit
F 06 Temperature sensor interruption or
temperature sensor short-circuit
F 07 Metering pump interruption or
metering pump short-circuit
F 08 Fan motor interruption or
fan motor short-circuit or
fan motor incorrect speed
F 09 Pencil-type glow plug interruption or
pencil-type glow plug short-circuit
F 10 Overheating
Air Top 2000 S