Filter Maintenance Alarm
Warns about the need to replace
the filter.
PROG
DEF
User
Description
Filter maintenance
P1050
2)
0
Δ
0 = disable
1 = enable and generates only alarm (A0770)
2 = enable and generates fault (F0771)
1)
P1051
5,000h
Filter maintenance time (0 to 32,000h)
P1052
2)
Ready parameter
Operation time for ilter maintenance
Notes: 1) A0770 will be generated on keypad during motor deceleration and the fault
F0771 after stopping the motor.
2) Set P1050 in “0” to reset the operation time for ilter maintenance alarm.
F0771
FAULT
1)
Stop the
system
P1051
Filter maintenance time (hours)
P1050 = 1
P1050 = 2
TIMER ON
P1052
2)
Operation time for filter maintenance
Time ON when the VFD is running
A0770
Alarm
Do not
stop the
system
Notes: Δ Setting depends on application.
1) Set P1050 in “0” to reset the operation time for ilter maintenance alarm.