WEG bacnet CFW701 Quick Setup Manual - page 5
www.weg.net
CFW700 HVAC-R Drives
5
PROG
DEF
User
Description
Basic application - BASIC group
P0100
20s
Δ
Acceleration time (s)
P0101
20s
Δ
Deceleration time (s)
P0133
90 rpm
Δ
Minimum speed (Hz)
P0134
1,800 rpm
Δ
Maximum speed (Hz)
Note: Δ Setting depends on application.
PROG
DEF
Description
Motor overload settings - PARAM group
P0156
1.05 x Inom-ND
Overload current at 105% speed
P0157
0.9 x Inom-ND
Overload current at 50% speed
P0158
0.65 x Inom-ND
Overload current at 5% speed
DEF
User
Description
Changing monitor display parameter - HMI group
P0205 = 2
P0206 = 1
1
Speed reference (rpm)
2
Output speed (rpm)
3
Motor current (A)
5
Output frequency (Hz)
7
Output voltage (V)
42
Time powered (h)
44
Output energy (kWh)
1011
Control setpoint 1
1015
Control process variable
DEF
User
Description
Changing main display unit - HMI group
P0209 = 3
3
rpm
11
°C
21
°F
22
bar
24
psi
36
gal/s
37
gal/min
40
l/min
50
m³/h
Rotation
Local/Remote
Status
Secondary display
P0206
Main display unit
P0209
Main display unit
P0205
Parameters
group