WEG bacnet CFW701 Quick Setup Manual - page 11
Other manuals for bacnet CFW701:
User Manual
of
16
www.weg.net
CFW700 HVAC-R Drives
11
Short Cycle Protection
Prevents compressor/motor from being
switched on and off in short period of times.
Run/stop commands are ignored, with the
exception of “general disable” and faults.
Compressor
function
protection
PROG
DEF
User
Description
Short cycle protection
P0585
0
1
0 = disable
1 = enable
P0586
5s
Δ
Minimum run time (0 to 650.00s)
P0587
Minimum stop time (0 to 650.00s)
Note: Δ Setting depends on application.
Switch VFD ON
Run
Enable command Switch VFD OFF
Stop
Enable command Switch VFD ON
Run
TIMER ON
P0587
Minimum STOP Time
TIMER ON
P0586
Minimum RUN Time
Switch VFD OFF
Stop