WEG CFW100 Installation And Operation Manual - Display (Cfw100)
Flash Memory Module
E
ng
lis
h
8 | CFW100
State
HMI
Description
PARAM
PASTE
ERROR
Indicates an error occurred in the
download
(CFW100-MMF
→ CFW100) of
the inverter parameter table.
SOFTPLC
PASTE
ERROR
Indicates an error occurred in the
download
(CFW100-MMF
→ CFW100) of
the inverter SoftPLC application.
The possible causes of the “ErrC” and “ErrP” errors are:
Low battery during the transfer.
Disconnection of the cable during the transfer.
Incompatibility of firmware versions during download
of the inverter parameter table (paste function)
indicating “ErrP” on the display.
6 INDICATIONS ON THE INVERTER
DISPLAY (CFW100)
State
HMI
Description
NORMAL
Normal operating condition.
FAULT
Indication of communication fault
between the CFW100-MMF and
the CFW100 (F082). This fault
can be reset by means of the
switch indicated in
Figure A.3 on
page 21
.
ALARM
Alarm indication in the attempt
to copy protected SoftPLC user
program from the CFW100.
The possible causes of F082 fault are:
Data transfer using the paste function
(CFW100-MMF
→ CFW100) with invalid data and/or
incompatible software version.
Attempt of connection and data transfer with the
(CFW100) inverter energized.
The possible causes of alarm A712 are:
Attempt to copy SoftPLC program protected against
copies (“never permit to copy").
Attempt to copy the SoftPLC program from a
protected copy ("never permit to copy from a copy").