WoodPro WS-TS-1500 Owner's Manual - page 11
PIPE SIZING
Single wall pipe is used to make the connection
from the final positioning of your stove to an approved
chimney. Pipe is
NOT included as part of the stove.
Pipe must be 6”/152mm diameter minimum of 24 MSG
(minimum standard gauge) black or 26 MSG blue steel
stove pipe.
NOTICE: FOR MOBILE HOME INSTALLATIONS
(US ONLY), PIPE MUST BE DOUBLE-WALL,
HIGH-TEMPURATURE PIPE
103 HT SPECIFI
THAT MEETS UL
CATIONS.
Any pipe used must be in good condition. Replace
if necessary before using stove. Pipe is not rated to
provide close contact to combustible materials and
must have proper clearance from com
-
bustible mater
ials as shown in the clearance diagrams on the previous
pages. Pipe should never be used in place of a chimney.
If
result.
proper clearances are not observed a house fire could
INSTALLATION INSTRUCTIONS
Please Note: Installation of a flue damper is NOT
recommended. Combustion control is regulated by the
intake of combustion air, not the exhaust.
1. The crimped end of the stovepipe fits inside the
stove flue collar. Secure with three (3) equally
spaced sheet metal screws. The first section of
connector pipe must be single walled to properly
attach to the stove collar. Install additional pipe and
elbow with the crimped end towards the stove. This
will allow any condensation in the flue to run back
into the firebox.
2. Horizontal pipe runs must slope upwards
towards the chimney at least 1/4˝/6.4mm per foot
of horizontal run.
3. You must have at least 18˝/457mm of clearance
between any horizontal piping and the ceiling.
4. The pipe cannot extend into the chimney flue
(figure 8).
5. Secure all pipe/elbow sections with three (3) equally
spaced sheet metal screws at each joint to make
the piping rigid. DO NOT CONNECT THIS STOVE
TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
6. It is recommended that no more than two (2)
90° bends be used in the stovepipe installa-
tion. The use of more than two 90° bends may
decrease the amount of draw and possibly
cause smoke spillage. Where possible, use only
corrugated (non adjustable) elbows. These
provide a better seal.
7. The pipe must not pass through an attic or roof
space, trusses, closet, or any concealed space, floor,
ceiling, wall, or combustible construction.
(See
Chimney Connector Systems & Clearances, page
17.) A manufactured chimney system listed to UL
103 HT (US)/ULC-S629 (CAN) must be used from
the first penetration of ceiling or wall to the chimney
cap.
Where passage through a wall or partition of com-
bustible construction is desired, the installation shall
conform to Chimney manufacturer’s instructions.
WARNING: DO NOT USE SINGLE WALL PIPE
AS A CHIMNEY - A HOUSE FIRE COULD
RESULT.
Figure 8 – Stovepipe/Flue Connections
NOTE: PIPE IS NOT INCLUDED. TO PURCHA- ,
SE VISIT YOUR LOCAL HARDWARE, HOME,
OR BUILDING CENTER.
ADDITIONAL SPECI-
FICATIONS.
11