2gig Technologies Go Control Install Manual - page 47
46
©2013 2GIG Technologies Inc. All Rights Reserved.
Go!Control Wireless Security System | Install Guide
Q-29 Enter periodic test, in days (0-
255)
DEFAULT: 30 days
Automatic test reports can be sent to the Central
Station every certain number of days.
•
The default (30) sends an automatic test
report every 30 days.
•
To set a different period for automatic test
reports, select (1‐255) days.
•
To disable automatic test reports, select (0).
Q-31 Enter cancel time, in minutes
(5-255)
DEFAULT: 5 minutes (Required SIA CP-
01 Minimum)
A cancel report will be sent to the Central Station
after an alarm, if the system is disarmed within the
programmed time.
•
The default (5) sets the cancel time at five
minutes.
•
For a longer cancel time, select (6‐254)
minutes.
•
To have the Control Panel always send a cancel
report when the system is disarmed after an
alarm, select (255).
NOTE:
See Q‐32 for information on displaying
when a cancel report is sent.
NOTE:
This default can be changed without
affecting SIA CP‐01 compliance.
Q-32 Select cancel display (0-1)
DEFAULT: Enabled (1) (Required SIA CP-
01 Default)
A cancel report will be sent to the Central Station
after an alarm, if the system is disarmed within the
programmed time. The Control Panel can also
display that a cancel report was sent.
•
The default (1) enables the cancel display
feature.
•
To turn off the cancel display feature, select
disabled (0).
NOTE:
See Q‐31 for information on setting the
cancel report trigger time.
NOTE:
This default can be changed without
affecting SIA CP‐01 compliance.
Q-33 Select cross sensor 47-48
(0-1)
DEFAULT: Disabled (0)
The Control Panel can be programmed so sensors
47 and 48 must both be violated during a set time
to trigger an alarm. This is called “cross sensor”
verification. When enabled, if only one sensor
(47or 48) is violated, the alarm will not trigger, but
a trouble report will be sent for the sensor that
triggered.
NOTE:
CO and fire zone cannot be used for
cross sensors.
•
The default (0) disables the cross sensor
feature.
•
To use the cross sensor feature, select enabled
(1).
NOTE:
See Q‐34 for information on setting the
cross sensor timeout.
Q-34 Enter cross sensor timeout, in
seconds (10-120)
DEFAULT: 10 seconds
The cross sensor timeout is the maximum period of
time allowed between violation of sensors 47 and
48 that will trigger an alarm. If both sensors are
violated within this time period, an alarm will be
triggered. If both sensors are not violated within
this time period, an alarm will not be triggered.
NOTE:
Cross sensor verification must be
enabled with Q‐33 for this feature to
function.
•
The default (10) sets the cross sensor timeout
at 10 seconds.
•
To change the cross sensor timeout duration,
select (11‐120) seconds.
Q-35 Select abort window dialer
delay (0-2)
DEFAULT: 30 seconds (1) (Required SIA
CP-01 Default)
The dialer (digital communicator) delays calling the
Central Station to allow the user enough time to
cancel a false alarm before it is reported.
•
The default (1) sets the dialer delay at 30
seconds.
•
To change the dialer delay, select (0) for 15
seconds or (2) for 45 seconds.
NOTE:
Per SIA CP‐01, the combination of the
Abort Window Dialer Delay (Q‐35) and
the Entry Delay (Q‐6 or Q‐7) cannot
exceed one minute.