36 OI/266/FF-EN Rev. B
| 2600T Series Pressure transmitters
10 HMI local indicator
10.2 TTG (Trough The Glass) version (L5 option)
TTG technology allows the user to operate on the keypad of
the HMI without the need of opening the windowed cover of
the transmitter. The capacitive pick-ups will detect the
presence of your finger in front of the respective button
activating the specific command. At the transmitter power-on
the HMI automatically calibrate its sensitivity, it is mandatory for
the proper functioning of the TTG HMI that the cover is properly
tightened at power-on.
In case the cover has been removed to access the
communication board, it is recommended to power off and
power-on again the transmitter once the windowed cover has
been set in place and properly tightened. For safety reasons
the keypad needs a specific activation procedure before to
become usable
10.3 Installing/Removing the LCD display
—
Unscrew the housing cover of the communication board/
LCD side.
—
Attach the LCD display. Depending on the mounting
position of the pressure transmitter, the LCD display may
be attached in four different positions. This enables ± 90°
or ± 180° rotations.
10.4 Operations
The HMI is a Dot matrix LCD with a keypad of 4 buttons
usable for different purposes.
— Variable Indicator
— Diagnostic Indicator
— Feedback of the local push button operations.
— Configuration tool
10.5 HMI as Variable Indicator
This is the normal way of how the HMI works. It is refreshed
every 2 seconds and can visualize the process measured
variables as well as other variables calculated every loop in the
PRTB and in the several Function Blocks. The HMI can be set
to four different operating Modes:
One line
Only one variable with its unit code is
displayed
One line and bar-graph
One variable with its unit code is displayed and
another variable can be selected to be dis-
played in percentage by the bar-graph
Two lines
Two variables with unit code are displayed
together (one for each line)
Two lines and bar-graph
Two variables with unit code are displayed
together (one for each line) and another vari-
able can be selected to be displayed in
percentage by the bar-graph
The Mode selection can be done through the remote setting of
the
HMI_MODE
parameter or locally from the HMI menu
“Display/Settings/Mode”
10. HMI local indicator
The 266 PdP is available with the integral HMI LCD local
indicator with 4 buttons keypad as optionally item connected
on the communication board. There are two types of available
HMI:
10.1 Conventional version (L1 option)
Gain access to the display by unscrewing the windowed cover.
Please observe the Hazardous area prescription before
proceeding with the cover removal.
The keypad operability doesn’t require any activation
procedure.
Figure 45: Display keypad
Important.
Retighten the housing cover until it is hand-tight.If
necessary, refer to the section “Securing the housing cover in
flameproof areas”.
Figure 46: Windowed front cover and LCD display